15 CORRECTION OF OBVIOUS ERRORS IN PUBLICATION  

  •  

    ORR # 2003-015

     

    Department of Labor and Economic Growth Construction Code

    January 24, 2005

     

    Mr. Brian Devlin, Director

    DMB, Office of Regulatory Reform 2nd Floor; Mason Building Lansing, MI  48933

     

    Dear Brian:

     

    Staff has detected errors in the following rules, as indicated in bold print below.  This rule set becomes effective on February 28, 2005.

     

    MICHIGAN UNIFORM ENERGY CODE

     

    R 408.31070  Heating energy analysis comparison report.

    Rule 1070.  Sections N1107.1, N1107.1.1, N1107.2, abbreviated report form N1107.1, and table N1107.1 are added to the code to read as follows:

    N1107.1  Heating energy analysis comparison report.  A heating energy comparison report shall be submitted to the code official to include both of the following information:

    1.    A basic description of the proposed alternate building design and any exceptions to the standard design criteria.

    2.    Abbreviated report form N1107.1, comparing the alternative house design with a standard design house complying with the provisions of this chapter through the systems analysis method.

    Abbreviated Report Form N1107.1 Heating Energy Analysis Comparison Report

     

    Text Box: Builder=s Name: Project Address:
City/Township/County:

     

    PROPOSED ALTERNATIVE HOUSE                                                                           STANDARD DESIGN HOUSE

    ROOF/CEILING (INC. SKYLIGHTS)                       SUBTOTALS                        ROOF/CEILING (INC. SKYLIGHTS)                                                                                 SUBTOTALS

    A1                


    /R1                   


    =  A1 /R1                  

     

    A2                


    /R2                   


    =  A2 /R2                  

     

    A3                


    /R3                   


    =  A3 /R3                  

     

     

    Total Roof/Ceiling Area


    A1 /R1 + A2 /R2 + A3 /R =                         

    Line 1


    x      0.0204 =

    Total Roof/Ceiling Area                             (all zones)


    Line A

     

    GROSS WALL                                                                                                       GROSS WALL

     

     

    Opaque Wall (Does not include band joist, windows, doors, etc.)

     

    A1                


    /R1                   


    =  A 1 /R1                  

     

    A2                


    /R2                   


    =  A 2 /R2                  

    A1 /R1 + A 2 /R2 =

     

    Line 2

     

    Band Joist

     

    A           /R               


    =  A /R             =


     

    Line 3

     

    Fenestration and Doors, Windows

     

    A1                


    /R1                   


    =  A1 /R1                  

     

    A2                


    /R2                   


    =  A2 /R2                  

     

    A3                


    /R3                   


    =  A3 /R3                  

    A1 /R1 + A2 /R2 + A3 /R3 =                        

    Line 4

     

    Doors

     

    A1                


    /R1                   


    =  A1 /R1                  

     

    A2                


    /R2                   


    =  A2 /R2                  

    A1 /R1 + A2 /R2 =


     

     

    Line 5

     

    Other

     

    A           /R               


    =  A/R                 =

     

    Total Gross Wall Area


    Line 6

     

    GROSS WALL SUBTOTAL A/R (Lines: 2+3+4+5+6)


    x      0.093 =                                

    Line 7


    Total Gross Wall Area                           (all zones)


    Line B

    Abbreviated Report Form N1107.1

     

     

    Heating Energy Analysis Comparison Report

    Continued

     

    FOUNDATION/FLOOR                             SUBTOTAL S


    FOUNDATION/FLOOR                       SUBTOTALS

     

    Floors Over Unconditioned Spaces


    Floors Over Unconditioned Spaces

     

     

    A                     /R                


     A/R                  =                                      


                                                            x       0.0204  =                              

    Line 8


    Total Floor Area                                            (all

    zones)


    Line C

     

    Slab on Grade Floors (Area = Perimeter x 2')


    Slab on Grade (Unheated)

     

    Z10.0909                                 


     A/R                 =                        

    Line 9


                                                            x       Z20.0769 =

    Total Slab Edge Area


    Line D

     

     

     

     

     

     

    Z30.050

     

    Slab on Grade (Heated)

    Z10.0769

                                                            x                                                      Z20.0667 =

    Total Slab Edge Area

    Z30.050

     

     

     

     

                       Line E

     

     

    Crawl Space Walls (Area:  Top foundation wall to average finished grade)

     

     

    A                 /R                     A/R                      =

     

     

     

     

                       Line 10

     

    Crawl Space

     

     

                                                            x       0.050 =

    Total Crawl Space Wall Area                                                                       (all

    zones)

     

     

     

     

                       Line F

     

    Basement Walls (Area:  Top foundation wall to average finished grade)

     

    A1                         /R1                               A1 /R1                               

     

    A2                         /R2                               A2 /R2                               

    A1 /R1 + A2 /R2 =

     

    Basement Windows

     

    A                 /R                     A/R                     =

     

     

     

     

     

     

                       Line 11

     

     

     

                       Line 12

     

    Basement Walls

     

     

     

     

     

    Z10.090

    x

     

     

     

     

     

     

     

    Line G

    Z20.090 =

    Total Gross Basement Wall Area

    Z30.055

    Total Gross Basement Wall Area

     

     

     

     

     

    FOUNDATION/FLOOR SUBTOTAL A/R (Lines:  8+9+10+11+12)

     

     

    Line 13

    FOUNDATION/FLOOR SUBTOTAL A/R (Lines:  C+D+E+F+G)

     

     

    Line H

    PROPOSED ALTERNATIVE HOUSE SUB-TOTAL

    A/R

    (Lines:  1+7+13)

     

                       Line 14

    STANDARD DESIGN HOUSE SUB-TOTAL

    A/R

    (Lines:  A+B+H)

     

     

    Line I

    HEATING EQUIPMENT EFFICIENCY

    (If the same as Standard House, go to line 16 or 17) (Oil or Gas Fired) AFUE:      %

    Line 14:               Adjusted A/R = AFUE: 0.      

     

     

     

     

     

                       Line 15

    HEATING EQUIPMENT EFFICIENCY

     

     

    (Oil or Gas Fired)              AFUE: 78%

     

    Line I:                  Adjusted A/R = AFUE: 0.78

     

     

     

     

     

     

    Line J

    AIR LEAKAGE RATE

    (If the same as Standard House, go to line 17)

     

                                          ACH x                                      ft3 x

    0.018 =

    Air Changes per Hour                          Volume of House

     

     

     

                       Line 16

    AIR LEAKAGE RATE

     

     

    0.55 ACH x ft3 x 0.018 = Volume of House

     

     

     

                       Line K

    PROPOSED ALTERNATIVE HOUSE TOTAL

    (Lines: 15+16)

     

    STANDARD DESIGN LIMIT TOTAL

    (Lines:  J+K)

     

     

     

     

    Equal to or less than line L to pass


    Line 17


    (Lines:  J+K)


    Line L

     

    Action and rationale:  Under Foundation Floors; Floors Over Unconditioned Spaces multiplier 0.0204 should be 0.0476.  Using the multiplier as printed will create an incorrect result when calculating for the proper R-value of insulation to be used for the construction to comply with the intent of the code. The version of the energy code that went to public hearing had the correct multiplier.

     

     

     

    Table N1107.1

    Alternative Standard Design Constants (1/r) for Systems Analysis Approach

     

    Heating Degree Days

    6000

    6500

    7000

    7500

    8000

    8500

     

    9000 +

    6499

    6999

    7499

    7999

    8499

    8999

    Roof/Ceiling

    0.0204

    0.0204

    0.0204

    0.0204

    0.0204

    0.0204

    0.0204

    Gross Wall

    0.093

    0.093

    0.093

    0.093

    0.093

    0.093

    0.093

    Foundation/floor Floor over

    unconditioned space

     

     

    0.0204

     

     

    0.0204

     

     

    0.0204

     

     

    0.0204

     

     

    0.0204

     

     

    0.0204

     

     

    0.0204

    Slab on grade Unheated slab

     

    0.0909

     

    0.0909

     

    0.0769

     

    0.0769

     

    0.0769

     

    0.050

     

    0.050

    Heated Slab

    0.0769

    0.0769

    0.0667

    0.0677

    0.0667

    0.050

    0.050

    Crawl space

    0.05

    0.05

    0.05

    0.05

    0.05

    0.05

    0.05

    Basement wall

    0.0909

    0.0909

    0.0909

    0.0909

    0.0909

    0.0555

    0.0555

     

    Action and rationale:  Under Foundation Floors; Floors Over Unconditioned Spaces multiplier 0.0204 should be 0.0476.  This needs to match the multiplier found in the Abbreviated Report Form N1107.1 to achieve proper calculation of R values for insulation. As printed, the multiplier calls for a higher R value than necessary resulting in the use of more insulation and a higher building cost.  Correcting the figure in both the Abbreviated Report form and table will result in a more realistic use of insulating materials and reduce the up front building costs.

     

    (Michigan Residential Code)


    TABLE N1102.1

    SIMPLIFIED PRESCRIPTIVE BUILDING ENVELOPE THERMAL COMPONENT CRITERIA MINIMUM REQUIRED THERMAL PERFORMANCE (U-FACTOR AND R-VALUE)

    Exterior Enclosure


    Zones

    1                              2                           3

    Wall Assemblies                                                                                                   R-21                       R-21                     R-21

    Fenestration/Openings (area weighted average of the total area of fenestration units)1,


    U =0.35 (R= 2.85)

    Roof/Ceiling Assemblies2                                                                                                                             R-49                       R-49                     R-49

    Floors over unconditioned spaces                                                                    R-21                       R-21                     R-21

    Slab on grade construction3

     

     

     

    R-11, 4 ft.               R-13, 4ft              R-18, 4ft

     

    Crawl space walls4                                                                                                                                               R-20                       R-20                     R-20 Continuous Insulation                              R-10                       R-10

     

     

    Basement walls


    R-15

    BUILDING LOCATION

    MAXIMUM GLAZINGGLA ZING U- FACTOR [Btu /

    . °

    (hr .ft F)]

    . °

    MINIMUM INSULATION R-VALUE [(hr .ft F) / Btu]

     

     

    Climate Zone

     

     

     

    HDD

     

     

     

    Ceilings

     

     

     

    Walls

     

     

     

    Floors

     

     

    Basement walls

    Slab perimeter R- value and depth /

     

     

    Crawl space walls

    1

    0-499

    Any

    R-13

    R-11

    R-11

    R-0

    R-0

    R-0

    2

    500-999

    0.90

    R-19

    R-11

    R-11

    R-0

    R-0

    R-4

    3

    1,000-

    1,499

    0.75

    R-19

    R-11

    R-11

    R-0

    R-0

    R-5

    4

    1,500-

    1,999

    0.75

    R-26

    R-13

    R-11

    R-5

    R-0

    R-5

    5

    2,000-

    2,499

    0.65

    R-30

    R-13

    R-11

    R-5

    R-0

    R-6

    6

    2,500-

    2,999

    0.60

    R-30

    R-13

    R-19

    R-6

    R-4, 2 ft.

    R-7

    7

    3,000-

    3,499

    0.55

    R-30

    R-13

    R-19

    R-7

    R-4, 2 ft.

    R-8

    8

    3,500-

    3,999

    0.50

    R-30

    R-13

    R-19

    R-8

    R-5, 2 ft.

    R-10

    9

    4,000-

    4,499

    0.45

    R-38

    R-13

    R-19

    R-8

    R-5, 2 ft.

    R-11

    10

    4,500-

    4,999

    0.45

    R-38

    R-16

    R-19

    R-9

    R-6, 2 ft.

    R-17

    11

    5,000-

    5,499

    0.45

    R-38

    R-18

    R-19

    R-9

    R-6, 2 ft.

    R-17

    12

    5,500-

    5,999

    0.40

    R-38

    R-18

    R-21

    R-10

    R-9, 4 ft.

    R-19

    13

    6,000-

    6,499

    0.35

    R-38

    R-18

    R-21

    R-10

    R-9, 4 ft.

    R-20

    14

    6,500-

    6,999

    0.35

    R-49

    R-21

    R-21

    R-11

    R-11, 4 ft.

    R-20

    15

    7,000-

    8,499

    0.35

    R-49

    R-21

    R-21

    R-11

    R-13, 4 ft.

    R-20

    16

    8,500-

    8,999

    0.35

    R-49

    R-21

    R-21

    R-18

    R-14, 4 ft.

    R-20

    17

    9,000-

    12,999

    0.35

    R-49

    R-21

    R-21

    R-19

    R-18, 4 ft.

    R-20

     

     
     

     

     

     


    Cavity Insulation

    R-11

    R-11

     

     

     

     

    R-19

     

    1 Fenestration units are required to meet this standard for the entire unit.

    2 Skylight U (1/R) factors are required to meet the fenestration requirements set forth in this table for fenestration/openings. Skylights are limited to 10% of the gross roof/ceiling area.

    3 See section N1102.1.6 for additional installation criteria.

    4 See section N1102.1.7 for additional installation criteria.

     

    Action & Rationale: Upon adoption of the International Residential Code, this table was amended for use in Michigan.  The original version of Table N1102.1 found in the International Residential Code includes the distance designation.  When the table was amended for the Michigan code the distance designation of 4 ft was inadvertently left out of the table. The distance of 4 ft needs to be added to the “zone” information for ‘slab on grade construction’ to correspond to the installation criteria in the related section N1102.1.6.

    Without this distance information it will be difficult for contractors and builders to comply with the intent of the code.

    (International Residential Code Table)

     

    TABLE N1102.1

    SIMPLIFIED PRESCRIPTIVE BUILDING ENVELOPE THERMAL COMPONENT CRITERIA MINIMUM REQUIRED THERMAL PERFORMANCE (U-FACTOR AND R-VALUE)

     

     

    Michigan Administrative Code.

     

    If you have any questions about this transmittal, please contact me at 241-4580. Sincerely,

     

    Norene Lind, Regulatory Affairs Officer MDLEG, Office of Policy and Legislative Affairs

     

     

     