ORR # 2003-015
Department of Labor and Economic Growth Construction Code
January 24, 2005
Mr. Brian Devlin, Director
DMB, Office of Regulatory Reform 2nd Floor; Mason Building Lansing, MI 48933
Dear Brian:
Staff has detected errors in the following rules, as indicated in bold print below. This rule set becomes effective on February 28, 2005.
MICHIGAN UNIFORM ENERGY CODE
R 408.31070 Heating energy analysis comparison report.
Rule 1070. Sections N1107.1, N1107.1.1, N1107.2, abbreviated report form N1107.1, and table N1107.1 are added to the code to read as follows:
N1107.1 Heating energy analysis comparison report. A heating energy comparison report shall be submitted to the code official to include both of the following information:
1. A basic description of the proposed alternate building design and any exceptions to the standard design criteria.
2. Abbreviated report form N1107.1, comparing the alternative house design with a standard design house complying with the provisions of this chapter through the systems analysis method.
Abbreviated Report Form N1107.1 Heating Energy Analysis Comparison Report
PROPOSED ALTERNATIVE HOUSE STANDARD DESIGN HOUSE
ROOF/CEILING (INC. SKYLIGHTS) SUBTOTALS ROOF/CEILING (INC. SKYLIGHTS) SUBTOTALS
A1
/R1
= A1 /R1
A2
/R2
= A2 /R2
A3
/R3
= A3 /R3
Total Roof/Ceiling Area
A1 /R1 + A2 /R2 + A3 /R =
Line 1
x 0.0204 =
Total Roof/Ceiling Area (all zones)
Line A
GROSS WALL GROSS WALL
Opaque Wall (Does not include band joist, windows, doors, etc.)
A1
/R1
= A 1 /R1
A2
/R2
= A 2 /R2
A1 /R1 + A 2 /R2 =
Line 2
Band Joist
A /R
= A /R =
Line 3
Fenestration and Doors, Windows
A1
/R1
= A1 /R1
A2
/R2
= A2 /R2
A3
/R3
= A3 /R3
A1 /R1 + A2 /R2 + A3 /R3 =
Line 4
Doors
A1
/R1
= A1 /R1
A2
/R2
= A2 /R2
A1 /R1 + A2 /R2 =
Line 5
Other
A /R
= A/R =
Total Gross Wall Area
Line 6
GROSS WALL SUBTOTAL A/R (Lines: 2+3+4+5+6)
x 0.093 =
Line 7
Total Gross Wall Area (all zones)
Line B
Abbreviated Report Form N1107.1
Heating Energy Analysis Comparison Report
Continued
FOUNDATION/FLOOR SUBTOTAL S
FOUNDATION/FLOOR SUBTOTALS
Floors Over Unconditioned Spaces
Floors Over Unconditioned Spaces
A /R
= A/R =
x 0.0204 =
Line 8
Total Floor Area (all
zones)
Line C
Slab on Grade Floors (Area = Perimeter x 2')
Slab on Grade (Unheated)
Z10.0909
= A/R =
Line 9
x Z20.0769 =
Total Slab Edge Area
Line D
Z30.050
Slab on Grade (Heated)
Z10.0769
x Z20.0667 =
Total Slab Edge Area
Z30.050
Line E
Crawl Space Walls (Area: Top foundation wall to average finished grade)
A /R = A/R =
Line 10
Crawl Space
x 0.050 =
Total Crawl Space Wall Area (all
zones)
Line F
Basement Walls (Area: Top foundation wall to average finished grade)
A1 /R1 = A1 /R1
A2 /R2 = A2 /R2
A1 /R1 + A2 /R2 =
Basement Windows
A /R = A/R =
Line 11
Line 12
Basement Walls
Z10.090
x
Line G
Z20.090 =
Total Gross Basement Wall Area
Z30.055
Total Gross Basement Wall Area
FOUNDATION/FLOOR SUBTOTAL A/R (Lines: 8+9+10+11+12)
Line 13
FOUNDATION/FLOOR SUBTOTAL A/R (Lines: C+D+E+F+G)
Line H
PROPOSED ALTERNATIVE HOUSE SUB-TOTAL
A/R
(Lines: 1+7+13)
Line 14
STANDARD DESIGN HOUSE SUB-TOTAL
A/R
(Lines: A+B+H)
Line I
HEATING EQUIPMENT EFFICIENCY
(If the same as Standard House, go to line 16 or 17) (Oil or Gas Fired) AFUE: %
Line 14: = Adjusted A/R = AFUE: 0.
Line 15
HEATING EQUIPMENT EFFICIENCY
(Oil or Gas Fired) AFUE: 78%
Line I: = Adjusted A/R = AFUE: 0.78
Line J
AIR LEAKAGE RATE
(If the same as Standard House, go to line 17)
ACH x ft3 x
0.018 =
Air Changes per Hour Volume of House
Line 16
AIR LEAKAGE RATE
0.55 ACH x ft3 x 0.018 = Volume of House
Line K
PROPOSED ALTERNATIVE HOUSE TOTAL
(Lines: 15+16)
STANDARD DESIGN LIMIT TOTAL
(Lines: J+K)
Equal to or less than line L to pass
Line 17
(Lines: J+K)
Line L
Action and rationale: Under Foundation Floors; Floors Over Unconditioned Spaces multiplier 0.0204 should be 0.0476. Using the multiplier as printed will create an incorrect result when calculating for the proper R-value of insulation to be used for the construction to comply with the intent of the code. The version of the energy code that went to public hearing had the correct multiplier.
Table N1107.1
Alternative Standard Design Constants (1/r) for Systems Analysis Approach
Heating Degree Days
6000 –
6500 –
7000 –
7500 –
8000 –
8500 –
9000 +
6499
6999
7499
7999
8499
8999
Roof/Ceiling
0.0204
0.0204
0.0204
0.0204
0.0204
0.0204
0.0204
Gross Wall
0.093
0.093
0.093
0.093
0.093
0.093
0.093
Foundation/floor Floor over
unconditioned space
0.0204
0.0204
0.0204
0.0204
0.0204
0.0204
0.0204
Slab on grade Unheated slab
0.0909
0.0909
0.0769
0.0769
0.0769
0.050
0.050
Heated Slab
0.0769
0.0769
0.0667
0.0677
0.0667
0.050
0.050
Crawl space
0.05
0.05
0.05
0.05
0.05
0.05
0.05
Basement wall
0.0909
0.0909
0.0909
0.0909
0.0909
0.0555
0.0555
Action and rationale: Under Foundation Floors; Floors Over Unconditioned Spaces multiplier 0.0204 should be 0.0476. This needs to match the multiplier found in the Abbreviated Report Form N1107.1 to achieve proper calculation of R values for insulation. As printed, the multiplier calls for a higher R value than necessary resulting in the use of more insulation and a higher building cost. Correcting the figure in both the Abbreviated Report form and table will result in a more realistic use of insulating materials and reduce the up front building costs.
(Michigan Residential Code)
TABLE N1102.1
SIMPLIFIED PRESCRIPTIVE BUILDING ENVELOPE THERMAL COMPONENT CRITERIA MINIMUM REQUIRED THERMAL PERFORMANCE (U-FACTOR AND R-VALUE)
Exterior Enclosure
Zones
1 2 3
Wall Assemblies R-21 R-21 R-21
Fenestration/Openings (area weighted average of the total area of fenestration units)1,
U =0.35 (R= 2.85)
Roof/Ceiling Assemblies2 R-49 R-49 R-49
Floors over unconditioned spaces R-21 R-21 R-21
Slab on grade construction3
R-11, 4 ft. R-13, 4ft R-18, 4ft
Crawl space walls4 R-20 R-20 R-20 Continuous Insulation R-10 R-10
Basement walls
R-15
BUILDING LOCATION
MAXIMUM GLAZINGGLA ZING U- FACTOR [Btu /
. °
(hr .ft2 F)]
. °
MINIMUM INSULATION R-VALUE [(hr .ft2 F) / Btu]
Climate Zone
HDD
Ceilings
Walls
Floors
Basement walls
Slab perimeter R- value and depth /
Crawl space walls
1
0-499
Any
R-13
R-11
R-11
R-0
R-0
R-0
2
500-999
0.90
R-19
R-11
R-11
R-0
R-0
R-4
3
1,000-
1,499
0.75
R-19
R-11
R-11
R-0
R-0
R-5
4
1,500-
1,999
0.75
R-26
R-13
R-11
R-5
R-0
R-5
5
2,000-
2,499
0.65
R-30
R-13
R-11
R-5
R-0
R-6
6
2,500-
2,999
0.60
R-30
R-13
R-19
R-6
R-4, 2 ft.
R-7
7
3,000-
3,499
0.55
R-30
R-13
R-19
R-7
R-4, 2 ft.
R-8
8
3,500-
3,999
0.50
R-30
R-13
R-19
R-8
R-5, 2 ft.
R-10
9
4,000-
4,499
0.45
R-38
R-13
R-19
R-8
R-5, 2 ft.
R-11
10
4,500-
4,999
0.45
R-38
R-16
R-19
R-9
R-6, 2 ft.
R-17
11
5,000-
5,499
0.45
R-38
R-18
R-19
R-9
R-6, 2 ft.
R-17
12
5,500-
5,999
0.40
R-38
R-18
R-21
R-10
R-9, 4 ft.
R-19
13
6,000-
6,499
0.35
R-38
R-18
R-21
R-10
R-9, 4 ft.
R-20
14
6,500-
6,999
0.35
R-49
R-21
R-21
R-11
R-11, 4 ft.
R-20
15
7,000-
8,499
0.35
R-49
R-21
R-21
R-11
R-13, 4 ft.
R-20
16
8,500-
8,999
0.35
R-49
R-21
R-21
R-18
R-14, 4 ft.
R-20
17
9,000-
12,999
0.35
R-49
R-21
R-21
R-19
R-18, 4 ft.
R-20
Cavity Insulation
R-11
R-11
R-19
1 Fenestration units are required to meet this standard for the entire unit.
2 Skylight U (1/R) factors are required to meet the fenestration requirements set forth in this table for fenestration/openings. Skylights are limited to 10% of the gross roof/ceiling area.
3 See section N1102.1.6 for additional installation criteria.
4 See section N1102.1.7 for additional installation criteria.
Action & Rationale: Upon adoption of the International Residential Code, this table was amended for use in Michigan. The original version of Table N1102.1 found in the International Residential Code includes the distance designation. When the table was amended for the Michigan code the distance designation of 4 ft was inadvertently left out of the table. The distance of 4 ft needs to be added to the “zone” information for ‘slab on grade construction’ to correspond to the installation criteria in the related section N1102.1.6.
Without this distance information it will be difficult for contractors and builders to comply with the intent of the code.
(International Residential Code Table)
TABLE N1102.1
SIMPLIFIED PRESCRIPTIVE BUILDING ENVELOPE THERMAL COMPONENT CRITERIA MINIMUM REQUIRED THERMAL PERFORMANCE (U-FACTOR AND R-VALUE)
Michigan Administrative Code.
If you have any questions about this transmittal, please contact me at 241-4580. Sincerely,
Norene Lind, Regulatory Affairs Officer MDLEG, Office of Policy and Legislative Affairs