3 ADMINISTRATIVE RULES  

  •  

     

    ORR # 2002-063

     

    DEPARTMENT OF LABOR AND ECONOMIC GROWTH DIRECTOR’S OFFICE  CONSTRUCTION CODE

    Filed with the Secretary of State on February 12, 2004.

    These rules take effect February 29, 2004

     

    (By authority conferred on the director of the department of labor and economic growth by section 4 of 1972 PA 230, MCL 125.1504, and Executive Reorganization Order Nos. 1996-2 and 2003-18, MCL

    445.2001 and 445.2011)

     

     

    R 408.30401, R 408.30404, R 408.30408, R 408.30409, R 408.30410, R 408.30411, R 408.30412, R

    408.30415a, R 408.30427, R 408.30429a, R 408.30437, R 408.30443, R 408.30445, R 408.30447, R

    408.30448d, R 408.30449, R 408.30458, R 408.30475, R 408.30499, R 408.30503, R 408.30505, R

    408.30506, R 408.30508, R 408.30510, R 408.30511, R 408.30512, R 408.30513, R 408.30514, R

    408.30515, R 408.30518, R 408.30519, R 408.30520, R 408.30521, R 408.30522, R 408.30524, R

    408.30526, R 408.30531, R 408.30534, R 408.30536, and R 408.30537 of the Michigan Administrative

    Code are amended, R 408.30414, R 408.30416, R 408.30417, R 408.30418, R 408.30419, R 408.30421,

    R 408.30444, R 408.30539, R 408.30540, R 408.30541, R 408.30542, R 408.30543, R 408.30544, R 408.30545, R 408.30546, and R 408.30547 are added to the Code, and R 408.30406, R 408.30461, R

    408.30495a, R 408.30517, and R 408.30523, of the Code are rescinded as follows:

     

    PART 4. BUILDING CODE

     

    R 408.30401 Applicable code.

    Rule 401. The provisions of the international building code, 2003 edition, including appendices F, G, and H, except for sections 104.8, 108.2 to 108.6, 112.2, 112.3, 114.3, 415.7.2.2 to 415.7.2.10, 415.7.3.1

    to 415.7.3.5.2, table 1608.2, 2902 to 2902.6.2, 3006.5, the definition of "recreational vehicle" in Appendix G, and, IECC-2003, ICC EC-2003, IMC-2003, IPC-2003, IPSDC-2003 listed in chapter 35, and the provisions of the international residential code, 2003 edition, including appendices A, B, C, D, E, F, G, J, K, and L, except for sections R104.8, R108.2, R108.3, R108.4, R108.5, R112.3, N1101 to N1104.1, tables N1101.2, N1102.1, N1102.1.1.1(1), N1102.1.1.1(2), N1102.1.1.2, N1102.4, N1103.1, N1103.5, and N1104.1, sections P2503.8, P2709.2.1, AJ102.4, and IBC-2003, ICC EC-2003, IECC-

    2003, IMC-2003, IPC-2003, NFPA 70-02 listed in chapter 43 govern the construction, alteration, relocation, demolition, use, and occupancy of buildings and structures, and, with exceptions noted, the international building code and the international residential code are adopted by reference in these rules. All references to the International Building Code, International Residential Code, International Energy Conservation Code, International Electrical Code, International Existing Building Code, International

     

     

    Mechanical Code, and International Plumbing Code mean the Michigan Building Code, Michigan Residential Code, Michigan Uniform Energy Code, Michigan Electrical Code, Michigan Rehabilitation Code for Existing Buildings, Michigan Mechanical Code, and Michigan Plumbing Code respectively. The codes are available for inspection at the Okemos office of the Michigan Department of Labor & Economic Growth, Bureau of Construction Codes and Fire Safety. The codes may be purchased from the International Code Council, 5203 Leesburg Pike, Suite 600, Falls Church, VA 22041, or from the Michigan Department of Labor & Economic Growth, Bureau of Construction Codes and Fire Safety, 2501 Woodlake Circle, Okemos, Michigan 48864, at a cost as of the time of adoption of these amendatory rules of $65.00 and $45.00, respectively.

     

    R 408.30404 Approval.

    Rule 404. Section 104.9 of the code is amended to read as follows:

    104.9. Approved materials and equipment. Materials, equipment, and devices shall be constructed or installed in accordance with approvals granted under section 21 of 1972 PA 230, MCL 125.1521 or by the building official.

     

    R 408.30406 Rescinded.

     

    R 408.30408 Fees.

    Rule 408. Section 108.1 of the code is amended to read as follows:

    108.1. Payment of fees. The fees prescribed by section 22 of 1972 PA 230, MCL 125.1522, shall be paid to the enforcing agency of the jurisdiction before a permit to begin work for new  construction, alteration, removal, demolition, or other building operation may be issued. In addition, an amendment to a permit necessitating an additional fee shall not be approved until the additional fee has been paid.

     

    R 408.30409 Permit.

    Rule 409. Sections 105.1.1, 105.1.2, and 105.2 of the code are amended to read as follows:

    105.1.1.    Annual permit. In place of an individual permit for each alteration to an already approved electrical, gas, mechanical, or plumbing installation, the enforcing agency is authorized to issue an annual permit upon application therefore to any person, firm, or corporation. The applicant shall be licensed in accordance with the requirements of 1956 PA 217, MCL 338.881 et seq., 1984 PA 192, MCL 338.971 et seq., or 2002 PA 733, MCL 338.3511 et seq.

    105.1.2.   Annual permit records. The person to whom an annual permit is issued shall keep a detailed record of alterations made under an annual permit. Access to the records shall be provided at all times and the records shall be filed with the enforcing agency.

    105.2. Work exempt from permit. Exemptions from permit requirements of the code shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of the code or any other laws or ordinances of this jurisdiction. Permits shall not be required for any of the following:

    (a)    Building permits shall not be required for any of the following:

    (i)    One-story detached accessory structures used as tool and storage sheds, playhouses and similar uses, provided the floor area does not exceed 120 square feet (11.15m2).

    (ii)    A fence that is not more than 6 feet (1829 mm) high.

    (iii)    Oil derricks.

    (iv)     A retaining wall that is not more than 4 feet (1219 mm) in height measured from the bottom of the footing to the top of the wall, unless supporting a surcharge or impounding class I, II or III-A liquids.

     

     

    (v)    A water tank supported directly upon grade if the capacity is not more than 5, 000 gallons (18 927 L) and the ratio of height to diameter or width is not greater than 2 to 1.

    (vi)     A sidewalk or driveway that is not more than 30 inches (762 mm) above grade and is not over any basement or story below and which are not part of an accessible route.

    (vii)     Painting, papering, tiling, carpeting, cabinets, counter tops and similar finish work.

    (viii)     Temporary motion picture, television and theater stage sets and scenery.

    (ix)     Prefabricated swimming pools accessory to a group R-3 occupancy, as applicable in section 101.2, which are less than 24 inches (610 mm) deep, do not exceed 5,000 gallons (19 000 L) and are installed entirely above ground.

    (x)     Shade cloth structures constructed for nursery or agricultural purposes and not including service systems.

    (xi)    Swings and other playground equipment accessory to 1- and 2-family dwellings.

    (xii)     Window awnings supported by an exterior wall which do not project more than 54 inches (1372 mm) from the exterior wall and do not require additional support of group R-3, as applicable in section

    101.2 and group U occupancies.

    (xiii)     Movable cases, counters, and partitions.

    (b)    Electrical permits shall not be required for any of the following:

    (i)    Repairs and maintenance: Minor repair work, including the replacement of lamps or the connection of approved portable electrical equipment to approved permanently installed receptacles.

    (ii)     Radio and television transmitting stations: The provisions of the code do not apply to electrical equipment used for radio and television transmissions, but do apply to equipment and wiring for power supply and to the installation of towers and antennas.

    (iii)     Temporary testing systems: A permit is not required for the installation of any temporary system required for the testing or servicing of electrical equipment or apparatus.

    (c)    Mechanical permits shall not be required for any of the following:

    (i)    Portable gas heating appliance.

    (ii)     Replacement of any minor part that does not alter approval of equipment or make the equipment unsafe.

    (iii)    Portable heating appliance.

    (iv)    Portable ventilation equipment.

    (v)    Portable cooling unit.

    (vi)    Steam, hot or chilled water piping within any heating or cooling equipment regulated by the code.

    (vii)     Replacement of any part that does not alter its approval or make it unsafe.

    (viii)     Portable evaporative cooler.

    (ix)    Self-contained portable refrigeration unit that is not more than 1.5 horsepower (1119 W).

    (d)    Plumbing permits shall not be required for any of the following:

    (i)     The stopping of leaks in drains, water, soil, waste, or vent pipe. However, if any concealed trap, drainpipe, water, soil, waste, or vent pipe becomes defective and it becomes necessary to remove and replace the drain or pipe with new material, then the work is considered new work and a permit shall be obtained and inspection made as provided in the code.

    (ii)    The clearing of stoppages or the repairing of leaks in pipes, valves, or fixtures, and the removal and reinstallation of water closets, if the repairs do not involve or require the replacement or rearrangement of valves, pipes, or fixtures.

     

    R 408.30410 Violations.

    Rule 410. Section 113.4 of the code is amended to read as follows:

     

     

    113.4. Violation penalties. It is unlawful for any person, firm, or corporation to violate a provision of the code or fail to conform with any of the requirements thereof, or erect, construct, alter, extend, repair, move, remove, demolish, or occupy any building, structure, or equipment regulated by the code, or cause work to be performed or done, in conflict with or in violation of the approved construction documents or directive of the enforcing agency, or a permit or certificate issued under the code. A violator shall be assessed a fine in accordance with section 23 of 1972 PA 230, MCL 125.1523.

     

    R 408.30411 Stop-work order.

    Rule 411. Section 114.2 of the code is amended to read as follows:

    114.2. Notice to owner. Upon notice from the enforcing agency, work on any building or structure that is being done contrary to the code or in a dangerous or unsafe manner shall immediately cease. Notice shall be in accordance with section 12 of 1972 PA 230, MCL 125.1512. A person who is served with a stop work order, except for work that the person is directed to perform to remove a violation or unsafe condition is subject to the penalty provisions prescribed in section 23 of 1972 PA 230, MCL 125.1523.

     

    R 408.30412 Certificate of use and occupancy.

    Rule 412. Section 110.1 of the code is amended to read as follows:

    110.1. Use and occupancy. A building or structure shall not be used or occupied, and a change in the existing occupancy classification of a building or structure or portion thereof shall not be made until a certificate of occupancy has been issued in accordance with section 13 of 1972 PA 230, MCL 125.1513.

     

    R 408.30414 Means of Appeal.

    Rule 414. Section 112.1 of the code is amended to read as follows:

    112.1 Means of appeal. A person may appeal a decision of the enforcing agency to the board of appeals. An application for appeal shall be based on a claim that the true intent of the code or the rules governing construction have been incorrectly interpreted, the provisions of the code do not apply, or an equal or better form of construction is proposed. The application shall be filed in accordance with section 14 of 1972 PA 230, MCL 125.1514.

     

    R 408.30415a Definitions.

    Rule 415a. The definitions of building, registered design professional, and structure in section 202 of the code are amended to read as follows:

    202. Definitions.

    "Building" means a combination of materials, whether portable or fixed, forming a structure affording a facility or shelter for use or occupancy by persons, animals, or property. The term does not include a building incidental to the use for agricultural purposes of the land on which the building is located if it is not used in the business of retail trade. The term shall be construed as though followed by the words "or part or parts of the building and all equipment in the building" unless the context clearly requires a different meaning.

    "Building official" means the person who is appointed and employed by a governmental subdivision charged with the administration and enforcement of the state code or codes and who is registered in accordance with the requirements of 1986 PA 54, MCL 338.2301 et seq.

    "Registered design professional" means an individual who is licensed under article 20, 1980 PA 299, MCL 339.2001 et seq.

    "Structure" means that which is built or constructed, an edifice or building of any kind, or a piece of work artificially built up or composed of parts joined together in some definite manner. Structure does not include a structure incident to the use for agricultural purposes of the land on which the structure is

     

     

    located and does not include works of heavy civil construction including without limitation any of the following:

    (a)    A highway.

    (b)    A bridge.

    (c)    A dam.

    (d)    A reservoir.

    (e)    A lock.

    (f)    A mine.

    (g)    A harbor.

    (h)    A dockside port facility.

    (i)    An airport landing facility.

    (j)    A facility for the generation, or transmission, or distribution of electricity.

    Structure shall be construed as though followed by the words "or part or parts of the structure and all equipment in the structure," unless the context clearly indicates otherwise.

     

    R 408.30416 Area and height increases.

    Rule 416. Section 406.3.6 of the code is amended to read as follows:

    406.3.6. Area and height increases. The allowable area and height of open parking garages shall be increased in accordance with the provisions of this section. Garages with sides open on 3/4 of the building perimeter are permitted to be increased by 25% in area and 1 tier in height. Garages with sides open around the entire building perimeter are permitted to be increased 50% in area and 1 tier in height. For a side to be considered open under the provisions of this rule, the total area of openings along the side shall not be less than 50% of the interior area of the side at each tier, and such openings shall be equally distributed along the length of the tier.

    Allowable tier areas in table 406.3.5 shall be increased for open parking garages constructed to heights less than the table maximum. The gross tier area of the garage shall not exceed that permitted for the higher structure. At least 3 sides of each such larger tier shall have continuous horizontal openings not less than 30 inches (762 mm) in clear height extending for at least 80% of the length of the sides, and no part of such larger tier shall be more than 200 feet (60 960mm) horizontally from such an opening. In addition, each such opening shall face a street or yard accessible to a street with a width of at least 30 feet (9144 mm) for the full length of the opening, and standpipes shall be provided in each such tier.

    Open parking garages of type II construction, with all sides open, shall be unlimited in allowable area where the height does not exceed 75 feet (22 860 mm). For a side to be considered open, the total area of openings along the side shall not be less than 50% of the interior area of the side at each tier, and such openings shall be equally distributed along the length of the tier. All portions of tiers shall be within 200 feet (60 960 mm) horizontally from such openings.

     

    R 408.30417 High-rise buildings.

    Rule 417. Sections 907.2.12 and 907.8.2 of the code are amended to read as follows:

    907.2.12. High-rise buildings. Buildings having floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communication system in accordance with section 907.2.12.2.

    Exceptions:

    1.  Airport traffic control towers in accordance with sections 412 and 907.2.22.

    2.  Open parking garages in accordance with section 406.3.

    3.  Buildings with an occupancy in group A-5.

     

     

    4.  Low-hazard special occupancies in accordance with section 503.1.2.

    5.  Buildings with an occupancy in group H-1, H-2, or H-3 in accordance with section 415.

    907.8.2. High-rise buildings. In buildings used for human occupancy that have floors located more than 55 (16 764 mm) above the lowest level of fire department vehicle access, a separate zone by floor shall be provided for all of the following types of alarm-initiating devices where provided:

    1.  Smoke detectors.

    2.  Sprinkler water-flow devices.

    3.  Manual fire alarm boxes.

    4.  Other approved types of automatic fire detection devices or suppression systems.

     

    R 408.30418 Maximum floor area allowances per occupant.

    Rule 418. Table 1004.1.2 of the code is amended to read as follows:

     

    Table 1004.1.2

    MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT

    OCCUPANCY

     

    FLOOR AREA IN SQ. FT. PER OCCUPANT

    Agricultural building

    300 gross

    Aircraft hangars

    500 gross

    Airport terminal

    Baggage claim Baggage handling Concourse Waiting areas

     

    20 gross

    300 gross

    100 gross

    15 gross

    Assembly

    Gaming floors (keno, slots, etc.)

     

    11 gross

    Assembly with fixed seats

    See section 1004.7

    Assembly without fixed seats

    Concentrated (chairs only-not fixed) Standing space

    Unconcentrated (tables and chairs)

     

    7 net

    5 net

    15 net

    Bowling centers, allow 5 persons for each lane

    including 15 feet of runway, and for additional areas

     

    7 net

    Business areas

    100 gross

    Courtrooms-other than fixed seating areas

    40 net

    Dormitories

    50 gross

    Educational

    Classroom area

    Shops and other vocational room areas Locker rooms

     

    20 net

    50 net

    15 gross

    Exercise rooms

    50 gross

    H-5 Fabrication and manufacturing areas

    200 gross

    Industrial areas

    100 gross

    Institutional areas

    Inpatient treatment areas Outpatient areas Sleeping areas

     

    240 gross

    100 gross

    120 gross

    Kitchens, commercial

    200 gross

    Library

    Reading rooms Stack area

     

    50 net

    100 gross

    Locker rooms

    50 gross

    Mercantile

     

     

     

    Areas on other floors  Basement and grade floor areas Storage, stock, shipping areas

    60 gross

    30 gross

    300 gross

    Parking garages

    200 gross

    Residential

    200 gross

    Skating rinks, swimming pools Rink and pool

    Decks

     

    50 gross

    15 gross

    Stages and platforms

    15 net

    Accessory storage areas, mechanical equipment room

     

    300 gross

    Warehouses

    500 gross

    For SI: 1 square foot = 0.0929 m2

     

    R 408.30419 Stadiums.

    Rule 419. Section 1008.2.1 of the code is amended to read as follows:

    1008.2.1. Stadiums. Panic hardware is not required on gates surrounding stadiums where such gates are under constant immediate supervision while public is present, and further provided that safe dispersal areas based on 3 square feet (0.28 m2) per occupant are located between the fence and enclosed space. Such required safe dispersal areas shall not be located less than 50 feet (15 240 mm) from the enclosed space.

     

    R 408.30421 Emergency escape and rescue.

    Rule 421. Section 1025.1 of the code is amended to read as follows:

    1025.1 General. In addition to the means of egress required by this chapter, provisions shall be made for emergency escape and rescue in group R as applicable in section 101.2, classrooms greater than 250 feet2 (23.2 m2) in group E, and group I-1 occupancies. Basements and sleeping rooms below the fourth story  above  grade  plane  shall  have  at  least  1  exterior  emergency  escape  and  rescue  opening  in accordance with this section. Where basements contain 1 or more sleeping rooms, emergency egress and rescue openings shall be required in each sleeping room, but shall not be required in adjoining areas of the basement. Such opening shall open directly into a public street, public alley, yard, or court. Exceptions:

    1.   In other than group R-3 occupancies as applicable in section 101.2, buildings equipped throughout with an approved automatic sprinkler system in accordance with section 903.3.1.1 or 903.3.1.2.

    2.   In other than group R-3 occupancies as applicable in section 101.2, sleeping rooms provided with a door to a fire-resistance-rated corridor having access to 2 remote exits in opposite directions.

    3.   The emergency escape and rescue opening is permitted to open onto a balcony within an atrium in accordance with the requirements of section 404, provided the balcony provides access to an exit and the dwelling unit or sleeping unit has a means of egress that is not open to the atrium.

    4.   Basements with a ceiling height of less than 80 inches (2032 mm) shall not be required to have emergency escape and rescue windows.

    5.  High-rise buildings in accordance with section 403.

    6.   Emergency escape and rescue openings are not required from basements or sleeping rooms which have an exit door or exit access door that opens directly into a public street, public alley, yard, egress court, or to an exterior exit balcony that opens to a public street, public alley, yard, or egress court.

    7.  Basements without habitable spaces and having not more than 200 square feet (18.6 square meters) in floor area shall not be required to have emergency escape windows.

     

    R 408.30427 Barrier free design for buildings, structures, and improved areas.

     

     

    Rule 427. Sections 1101.2 and 1109.7 of the code are amended and section 1103.2.15 is added to the code to read as follows:

    1101.2 Design. Buildings and facilities shall be designed and constructed to be accessible in accordance with this code and ICC A 117.1, except sections 611 and 707.

    1109.7 Lifts. Platform (wheelchair) lifts are permitted to be a part of a required accessible route in new construction where indicated in items 1 to 7. Platform (wheelchair) lifts shall be installed in accordance with the Michigan elevator code, R 408.8101 to R 408.8695.

    1.  An accessible route to a performing area and speakers' platforms in occupancies in group A.

    2.   An accessible route to wheelchair spaces required to comply with the wheelchair space dispersion requirements of sections 1108.2.2 to 1108.2.4.

    3.   An accessible route to spaces that are not open to the general public with an occupant load of not more than 5.

    4.  An accessible route within a dwelling or sleeping unit.

    5.     An accessible route to wheelchair seating spaces located in outdoor dining terraces in A-5 occupancies where the means of egress from the dining terraces to a public way are open to the outdoors.

    6.   An accessible route to raised judges' benches, clerks' stations, jury boxes, witness stands, and other raised or depressed areas in a court.

    7.  An accessible route where existing exterior site constraints make use of a ramp or elevator infeasible.

    1103.2.15. Military, fire service, and police facilities. Housing, bathing, toilet, training, and storage areas intended for use and occupancy exclusively by military, fire service, police, or security personnel required to be physically agile are not required to be accessible.

     

    R 408.30429a Compliance.

    Rule 429a. The code is amended by adding sections 3410.1 and 3410.2 as follows:

            Compliance. The provisions of this section are intended to maintain or increase the current degree of public safety, health, and general welfare in existing buildings while permitting repair, alteration, addition, and change of occupancy without requiring full compliance with chapters 2 through 33 of the code, or sections 3401.3 through 3407, except where compliance with other provisions of the code is specifically required in this section.

    Exception: Buildings made to comply with the provisions of the Michigan rehabilitation code for existing buildings, R 408.30551 to R 408.30577, shall be deemed to comply with the requirements of the code.

            Applicability. Structures existing before November 6, 1974, in which work involving additions, alterations, or changes of occupancy shall be made to conform to the requirements of this section or the provisions of sections 3402 to 3406 of the code.

    The provisions in sections 3410.2.1 to 3410.2.5 of the code shall apply to existing occupancies that will continue to be, or are proposed to be, in groups A, B, E, F, M, R, S, and U. These provisions shall not apply to buildings that have occupancies in group H or I.

     

    R 408.30437 Truss design drawings.

    Rule 437. Section 2303.4.1 of the code is amended to read as follows:

    2303.4.1 Truss design drawings. Truss construction documents shall be prepared by a registered design professional and shall be provided to the building official and approved prior to installation. These construction documents shall include, at a minimum, the following information. Truss shop drawings shall be provided with the shipment of trusses delivered to the job site.

    1.  Slope or depth, span and spacing.

     

     

    2.  Location of joints.

    3.  Required bearing widths.

    4.  Design loads as applicable.

    5.  Top chord live load (including snow loads).

    6.  Top chord dead load.

    7.  Bottom chord live load.

    8.  Bottom chord dead load.

    9.  Concentrated loads and their points of application.

    10.  Controlling wind and earthquake loads.

    11.  Adjustments to lumber and metal connector plate design value for conditions of use.

    12.  Each reaction force and direction.

    13.    Metal connector plate type, size, thickness or gage, and the dimensioned location of each metal connector plate except where symmetrically located relative to the joint interface.

    14.  Lumber size, species, and grade for each member.

    15.  Connection requirements are required for all of the following:

    a.   Truss to truss girder.

    b.   Truss ply to ply.

    c.   Field species.

    16.  Calculated deflection ratio or maximum deflection for live and total load.

    17.   Maximum axial compression forces in the truss members to enable the building designer to design the size, connections, and anchorage of the permanent continuous lateral bracing. Forces shall be shown on the truss construction documents or on supplemental documents.

    18.  Required permanent truss member bracing location.

     

    R 408.30443 Masonry. Rule 443. Section 1405.3.2 of the code is amended to read as follows:

    1405.3.2. Masonry. Flashing and weep holes shall be located in the first course of masonry above finished ground level above the foundation wall or slab; at the heads of windows, doors, and other wall openings; at window sills and at other points of support including structural floors, shelf angles, and lintels where anchored veneers are designed in accordance with section 1405.5. Flashing shall extend to, or beyond, the finished face of the wall.

     

    R 408.30444. Water -resistive barrier.

    Rule 444. Section 1404.2 of the code is amended to read as follows:

    1404.2. Water-resistive barrier. A minimum of 1 layer of No. 15 asphalt felt, complying with ASTM D 226, as listed in chapter 43, for type 1 felt, shall be attached to the studs or sheathing, with flashing as described in section 1405.3, in such a manner as to provide a continuous water-resistive barrier behind the exterior wall veneer.

     

    R 408.30445 Automatic sprinkler systems.

    Rule 445. Section 903.2.10.3 of the code is amended to read as follows:

    903.2.10.3. Buildings more than 30 feet in height. An automatic sprinkler system shall be installed throughout a building that has a floor level which has an occupant load of 30 or more occupants and which is located 30 feet or more above the lowest level of fire department vehicle access.

    Exceptions:

    1.  Airport control towers.

    2.  Open parking structures.

    3.  Occupancies in group F-2.

    70506040

     

    4.  Existing buildings having occupied floor levels not more than 55 feet in height above the lowest level of fire department vehicle access, where the local unit of government complies with the following parameters:

    4.1.   The local unit of government having a municipal fire department with an ISO rating of 3 or lower, employing a full time career fire fighting staff.

    4.2.  The governing body of the local unit of government has passed a resolution affirming the use of this exception and filed that resolution with the department of labor & economic growth, bureau of construction codes and fire safety.

     

    R 408.30447 Smokeproof enclosures.

    Rule 447. Section 1019.1.8 of the code is amended to read as follows:

    1019.1.8. Smokeproof enclosures. In buildings required to comply with section 403 or 405 of the code, each of the exits of a building that serves stories where the floor surface is located more than 55 feet (16,764 mm) above the lowest level of fire department vehicle access or more than 30 feet (9,144 mm) below the level of exit discharge serving such floor levels shall be a smokeproof enclosure or pressurized stairway in accordance with section 909.20 of the code.

     

    R 408.30448d Ground snow loads.

    Rule 448d. Figure 1608.2 of the code is amended to read as follows:

     

    FIGURE 1608.2

     

     
    100908070706060Ground Snow Loads

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    3530255020R 408.30449 Frost protection.

     

     

    Rule 449. Section 1805.2.1 of the code is amended to read as follows:

    1805.2.1. Frost protection. Except where otherwise protected from frost, foundation walls, piers, and other permanent supports of buildings and structures shall be protected from frost by at least one of the following methods:

    1.  Extending not less than 42 inches below finish grade.

    2.  Constructing in accordance with ASCE-32 listed in chapter 35.

    3.  Erecting on solid rock. Exceptions:

    1.  Free-standing buildings meeting all of the following conditions shall not be required to be protected:

    a.   Classified in importance category I (see table 1604.5).

    b.   Area of 400 square feet (37 m2) or less.

    c.   Eave height of 10 feet (3048 mm) or less.

    2.   Upon evidence of the existence of any of the following conditions, the building official may modify the footing depth accordingly:

    a.   Freezing temperatures.

    b.   Soil type.

    c.   Groundwater conditions.

    d.  Snow depth experience.

    e.   Exposure to the elements.

    f.  Other specific conditions identified by the building official that may affect the foundation system. Footings shall not bear on frozen soil unless such frozen condition is of a permanent character.

     

    R 408.30458 Elevators and conveying systems.

    Rule 458. Sections 3001.1, 3001.2, 3001.4, 3002.5, 3002.6, 3003.2, 3004.5, and 3004.6 of the code are

    amended and sections 3001.2.1 and 3001.2.2 are added to the code to read as follows:

            Scope. The design, construction, installation, alteration, and repair of elevators and conveying systems and their equipment shall conform with the requirements of the Michigan elevator laws and rules, MCL 408.801 et seq., MCL 338.2151 et seq., and

    R 408.8101 to R 408.8695 and this chapter. Installation or construction in flood hazard areas established in section 1612.3 shall comply with ASCE 24 listed in chapter 35.

            Other devices. Other devices shall conform to the requirements of sections 3001.2.1 and

    3001.2.2 of the code.

            Conveyors. Conveyors and related equipment shall conform to the requirements of ASME B20.1 listed in chapter 35.

            Automotive lifts. Automotive lifts shall conform to the requirements of ALI ALCTV listed in chapter 35.

    3001.4. Change in use. A change in use of an elevator from freight to passenger, passenger to freight, or from 1 freight class to another freight class shall comply with the requirements of the Michigan elevator code, R 408.8101 to R 408.8695.

            Emergency doors. Where an elevator is installed in a single blind hoistway or on the outside of a building, there shall be installed in the blind portion of the hoistway or blank face of the building, an emergency door in accordance with the requirements of the Michigan elevator code, R 408.8101 to R 408.8695.

            Prohibited doors. Doors, other than hoistway doors and the elevator car door, shall be prohibited at the point of access to an elevator car.

     

     

    3003.2 Fire-fighters' emergency operation. Elevators shall be provided with phase I emergency recall operation and phase II emergency in-car operation in accordance with the requirements of the Michigan elevator code, R 408.8101 to R 408.8695.

            Plumbing and mechanical systems. Plumbing and mechanical systems shall not be located in an elevator shaft.

    Exception: Floor drains, sumps, and sump pumps exclusively for draining the elevator pit shall be permitted at the base of the shaft provided they are indirectly connected to the plumbing system.

            Construction at bottom of hoistway. Pits extending to the ground shall have noncombustible floors and be designed as to prevent entry of ground water into the pit. The pit floor of any hoistway not extending to the ground shall be of fire-resistive construction having a fire-resistance rating at least equal to that required for the hoistway enclosure.

     

    R 408.30461 Rescinded.

     

    R 408.30475 Existing structures.

    Rule 475. Sections 3409.1, 3409.3, 3409.5, 3409.6, and 3409.7.2 of the code are amended to read as follows:

    3409.1. Scope. The provisions of sections 3409.2 to 3409.8.5 of the code apply to the maintenance, change of occupancy, additions, and alterations to existing buildings, including those identified as historic buildings in accordance with 1966 PA 1, MCL 125.1351 et seq.

    3409.3. Change of occupancy. Unless technically infeasible, section 3409.5 of the code shall be applied in accordance with 1966 PA 1, MCL 125.1351 et seq.

            Alterations. A building, facility, or element that is altered shall comply with the applicable provisions in chapter 11 of the code and ICC/ANSI A117.1 listed in chapter 35, unless technically infeasible. When compliance with this section is technically infeasible, then the alteration shall provide access to the maximum extent technically feasible.

    Exceptions:

    1.   The altered element or space is not required to be on an accessible route, unless required by section

    3409.6 of the code.

    2.   Accessible means of egress required by chapter 10 of the code are not required to be provided in existing buildings and facilities.

    3.   Buildings, structures, or improved areas which exist on or before the effective date of these rules and which are in compliance with the code at the time of the issuance of the certificate of occupancy unless the alteration specifically modifies an area covered by sections 3409.6 to 3409.8.5 of the code.

            Alterations affecting an area containing a primary function. When an alteration affects the accessibility to, or contains an area of primary function, then the route to the primary function area shall be accessible. The accessible route to the primary function shall include accessible toilets and drinking fountains serving the area of the primary function.

    Exceptions:

    1.    The costs of providing the accessible route is not required to exceed 20% of the costs of the alterations affecting the area of primary function.

    2.   This section does not apply to alterations limited solely to windows, hardware, operating controls, electrical outlets, and signs.

    3.  This section does not apply to alterations limited solely to mechanical systems, electrical systems, the installation or alteration of fire-protection systems, and the abatement of hazardous materials.

    4.    This section does not apply to alterations undertaken for the primary purpose of increasing the accessibility of an existing building, facility, or element.

     

     

    3409.7.2. Elevators. Altered elements of existing elevators shall comply with the Michigan elevator code, R 408.8101 to R 408.8695 and ICC A 117.1. Such elements shall also be altered in elevators programmed to respond to the same hall call control as the altered elevator.

     

    R 408.30495a Rescinded.

     

    R 408.30499 Adoption of standards by reference; referenced codes.

    Rule 499. Chapter 35 of the code is amended to add the following referenced codes, which are available from the Michigan Department of Labor & Economic Growth, Bureau of Construction Codes and Fire Safety, 2501 Woodlake Circle, Okemos, Michigan 48864:

     

    (a)    Michigan Electrical Code                          R 408.30801 et seq., of the Michigan Administrative Code.

    (b)    Michigan Mechanical Code                       R 408.30901a et seq., of the Michigan Administrative Code.

    (c)    Michigan Plumbing Code                          R 408.30701 et seq., of the Michigan Administrative Code.

    (d)    Michigan Uniform Energy Code               R 408.31061 et seq., of the Michigan Administrative Code.

    (d) Michigan Elevator Code                            R 408.8101 et seq., of the Michigan Administrative Code.

     

    RESIDENTIAL CODE

     

    R 408.30503 Approved materials and equipment.

    Rule 503. Sections R104.9 of the code is amended to read as follows:

    R104.9. Approved materials and equipment. Materials, equipment, and devices shall be constructed or installed in accordance with approvals granted under section 21 of 1972 PA 230, MCL 125.1521 or by the building official.

     

    R 408.30505 Work exempt from permit.

    Rule 505. Section R105.2 of the code is amended to read as follows:

    R105.2. Work exempt from permit. Exemption from the permit requirements of the code shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of the code or any other laws or ordinances of this jurisdiction. Permits are not required for any of the following:

    (a)    Building permits shall not be required for any of the following:

    (i)    One-story detached accessory structures, if the floor area does not exceed 200 square feet (18.58 m2).

    (ii)    A fence that is not more than 6 feet (1829 mm) high.

    (iii)    A retaining wall that is not more than 4 feet (1219 mm) in height measured from the bottom of the footing to the top of the wall, unless supporting a surcharge.

    (iv)     A water tank supported directly upon grade if the capacity is not more than 5,000 gallons ( 18 927

    L) and the ratio of height to diameter or width is not greater than 2 to 1.

    (v)     A sidewalk or driveway that is not more than 30 inches (762 mm) above adjacent grade and is not over any basement or story below.

    (vi)    Painting, papering, tiling, carpeting, cabinets, counter tops, and similar finish work.

    (vii)     A prefabricated swimming pool that is less than 24 inches (610 mm) deep.

    (viii)     Swings and other playground equipment accessory to a 1- or 2-family dwelling.

    (ix)     Window awnings supported by an exterior wall which do not project more than 54 inches (1372 mm) from the exterior wall and do not require additional support.

    (b)    Electrical permits shall not be required for the following;

     

     

    Repairs and maintenance: A permit is not required for minor repair work, including the replacement of lamps or the connection of approved portable electrical equipment to approved permanently installed receptacles.

    (c)    Mechanical permits shall not be required for any of the following:

    (i)    Portable heating, cooking, or clothes drying appliances.

    (ii)     Replacement of any minor part that does not alter approval of equipment or make the equipment unsafe.

    (iii)    A portable heating appliance.

    (iv)    A portable ventilation appliance.

    (v)    A portable cooling unit.

    (vi)    Steam, hot or chilled water piping within any heating or cooling equipment regulated by the code.

    (vii)     Replacement of any minor part that does not alter approval of equipment or make the equipment unsafe.

    (viii)     A portable evaporative cooler.

    (ix)    A self-contained portable refrigeration unit that is not more than 1.5 horsepower (1119 W).

    (x)       Portable fuel cell appliances that are not connected to a fixed piping system and are not interconnected to a power grid.

    (xi)    Gas piping limited to 10 feet (3048 mm) in length and not more than 6 fittings.

    (d)    Plumbing permits shall not be required for any of the following:

    (i)     The stopping of leaks in drains, water, soil, waste or vent pipe; if any concealed trap, drainpipe, water, soil, waste or vent pipe becomes defective and it becomes necessary to remove and replace the same with new material, then the work is considered as new work and a permit shall be obtained and inspection made as provided in the code.

    (ii)    The clearing of stoppages or the repairing of leaks in pipes, valves, or fixtures, and the removal and reinstallation of water closets, if the repairs do not involve or require the replacement or rearrangement of valves, pipes, or fixtures.

     

    R 408.30506 Submittal documents.

    Rule 506. Sections R106.1 and R802.10.1 of the code are amended and section R106.1.4 and figure

    802.10.1 are added to the code to read as follows:

    R106.1. Submittal documents. Construction documents, special inspection and structural program and other data shall be submitted in 1 or more sets with each application for a permit. The construction documents shall be prepared by or under the direct supervision of a registered design professional when required by article 20 of 1980

    PA 299, MCL 339.101 et seq., and known as the Michigan occupational code. Where special conditions exist, the building official is authorized to require additional construction documents to be prepared by a registered design professional.

    R106.1.4. Truss design data. As an alternative to the submission of truss design drawings, the truss design data sheet may be provided to the building official as part of the construction documents at the time of application. Truss design drawings shall be submitted to the building official prior to truss installation as required by section R802.10.1.

    R802.10.1 Truss design drawings. Truss design drawings, prepared in conformance with section R802.10.1, shall be provided to the building official and approved prior to installation. The truss design data sheet, figure R802.10.1, may be provided to the building official at the time of permit application, as an alternative to design drawings as permitted in section R106.1.4. Truss design drawings shall include, at a minimum, the information specified below. Truss design drawings shall be provided with the shipment of trusses delivered to the jobsite.

     

     

    1.  Slope or depth, span, and spacing.

    2.  Location of all joints.

    3.  Required bearing widths.

    4.  Design loads as applicable.

    a.   Top chord live load (including snow loads).

    b.   Top chord dead load.

    c.   Bottom chord live load.

    d.  Bottom chord dead load.

    e.   Concentrated loads and their points of application.

    f.  Controlling wind and earthquake loads.

    5.  Adjustments to lumber and joint connector design values for conditions of use.

    6.  Each reaction force and direction.

    7.   Joint connector type and description (e.g., size, thickness, or gauge) and the dimensioned location of each joint connector except where symmetrically located relative to the joint interface.

    8.  Lumber size, species, and grade for each member.

    9.  Connection requirements for the following:

    a.   Truss to truss girder.

    b.   Truss ply to ply.

    c.   Field splices.

    10.  Calculated deflection ratio and/or maximum description for live and total load.

    11.   Maximum axial compression forces in the truss members to enable the building designer to design the size, connections, and anchorage of the permanent continuous lateral bracing. Forces shall be shown on the truss design drawing or on supplemental documents.

    12.  Required permanent truss member bracing location.

     

     

     

    Jurisdictional information should be included in this space

    Applicant's Name:

    Date:

    Applicant's Address:

    Permit Number:

    City:

    State:

    Zip:

    Applicant's Signature:

    Job Location:

    Address:

    Township/Village/City:

    County:

     

     
    Roof Loading Data Sheet

    Authority: 1972 PA 230                                                              Completion:

    Completed prior to application for plan review and building permit.  This form is a voluntary form used to assist in the permit approval process.

     

     

     

     

     

     

     

     

     

     

     

     

    THIS FORM SHOULD BE COMPLETED BY THE PERMIT APPLICANT, OR DESIGN PROFESSIONAL

    FOR Ce, Ct, AND I, PLACE AN "X" IN THE APPROPRIATE BOX  THAT BEST DESCRIBES THE STRUCTURE.

     

    Ground Exposure, Pg =                                       


    From Figure R301.2(5) MRC or Figure 1608.2 MBC

     

    Exposure Factor Ce

    Exposure

    Fully

    Exposed1

    Partially

    Exposed2

    Sheltered3

    A

    Large city center with at least 1/2 the buildings exceeding 70 ft. in height.

    N/A

     

    1.1

     

    1.3

     

    B

    Urban and suburban areas, wooded areas or other terrain with closely spaced objects having the size of single-family dwellings or larger.

    0.9

     

    1

     

    1.2

     

    C

    Open terrain with scattered obstructions having heights less than 30 ft.  (flat open country)

    0.9

     

    1

     

    N/A

     

    D

    Flat unobstructed areas exposed to wind flowing over open water for a distance of at least 1 mile.  (i.e. Great Lakes.)

     

    0.8

     

     

    0.9

     

     

    N/A

     

    1Fully Exposed: Roofs exposed on all sides with no shelter by terrain, higher structures, or trees. 2Partially Exposed:  All roofs except those designated as "fully exposed" or "sheltered." 3Sheltered: Roofs located tight among conifers that qualify as obstructions.

    Thermal Factor Ct

    Thermal Condition4

    Ct

    All structures except as listed below

    1

     

    Structures kept just above freezing and those with cold, ventilated roofs with an R factor of 25 or greater between the ventilated and heated spaces, such as attics

    1.1

     

    Unheated structures and those intentionally kept below freezing, such as seasonal building or storage buildings

    1.2

     

    Continuously heated greenhouse with a roof R Value less than 2 and having an interior temperature maintained at about 50 degrees 3 ft above the floor during winter months and a temperature alarm system or an attendant to warn of a heating failure.

     

    0.85

     

    4These conditions shall be representative of the anticipated conditions during winter months for the life of the structure

    Importance Factor

    Category

    I

    I

    Building and other structures representing low hazard to human life, i.e.: Agricultural, Temporary, and Minor Storage Facilities.

    0.8

     

    II

    All buildings except those listed in Categories III and IV.

    1

     

    III

    Building and other structures representing substantial hazard to human life in the event of failure.

    1.1

     

    IV

    Buildings and other structures designated as essential facilities.

    1.2

     

     

    Attic Live Load

    Entire Attic

    Y/N

    Specific Areas (if yes, list areas below)

    Y/N

    List Rooms:

     

     

     

     

    25

     

     

    R 408.30508 Payment of fees.

    Rule 508. Section R108.1 of the code is amended to read as follows:

    R108.1. Fees. The fees prescribed in section 22 of 1972 PA 230, MCL 125.1522 shall be paid to the enforcing agency of the jurisdiction before a permit to begin work for new construction, alteration, removal, demolition, or other building operation may be issued. In addition, an amendment to a permit necessitating an additional fee shall not be approved until the additional fee is paid.

     

    R 408.30510 Use and occupancy.

    Rule 510. Sections R110.1 and R110.2 of the code are amended to read as follows:

    R110.1. Use and occupancy. A building or structure shall not be used or occupied, and a change in the existing occupancy classification of a building or structure or portion thereof shall not be made until a certificate of occupancy has been issued in accordance with section 13 of 1972 PA 230, MCL 125.1513. R110.2. Change in use. A change in the character or use of an existing structure shall not be made, except as specified in the Michigan building code, R 408.30401 to

    R 408.30499a.

     

    R 408.30511 Violation penalties.

    Rule 511. Section R113.4 of the code is amended to read as follows:

    R113.4. Violation penalties. It is unlawful for any person, firm, or corporation to violate a provision of the code or fail to conform with any of the requirements thereof, or erect, construct, alter, extend, repair, move, remove, demolish, or occupy any building, structure, or equipment regulated by the code, or cause work to be performed or done in conflict with or in violation of the approved construction documents or directive of the enforcing agency, or a permit or certificate issued under the code. A violator shall be assessed a fine in accordance with section 23 of 1972 PA 230, MCL 125.1523.

     

    R 408.30512 Notice to owner.

    Rule 512. Section R114.1 of the code is amended to read as follows:

    R114.1. Notice to owner. Upon notice from the enforcing agency, work on any building or structure that is being done contrary to the code or in a dangerous or unsafe manner shall immediately cease. The notice shall be in accordance with section 12 of 1972 PA 230, MCL 125.1512. Any person who is served with a stop work order, except for work that the person is directed to perform to remove a violation or unsafe condition is subject to the penalty provisions in section 23 of 1972 PA 230, MCL 125.1523.

     

    R 408.30513 Definitions.

    Rule 513. The definitions of building, registered design professional, and sunroom addition in section R202 of the code are amended, the definition of residential building type is deleted, and the definition of structure is added to section R202 to read as follows:

    R202. Definitions.

    "Building" means a combination of materials, whether portable or fixed, forming a structure affording a facility or shelter for use or occupancy by persons, animals, or property. The term does not include a building incidental to the use for agricultural purposes of the land on which the building is located if it is not used in the business of retail trade. The term shall be construed as though followed by the words "or part or parts of the building and all equipment in the building" unless the context clearly requires a different meaning.

    "Registered design professional" means an individual who is licensed under article 20, 1980 PA 299, MCL 339.2001 et seq.

     

     

    "Structure" means that which is built or constructed, an edifice or building of any kind, or a piece of work artificially built up or composed of parts joined together in some definite manner. Structure does not include a structure incident to the use for agricultural purposes of the land on which the structure is located and does not include works of heavy civil construction including without limitation any of the following:

    (a)    A highway.

    (b)    A bridge.

    (c)    A dam.

    (d)    A reservoir.

    (e)    A lock.

    (f)    A mine.

    (g)    A harbor.

    (h)    A dockside port facility.

    (i)    An airport landing facility.

    (j)    A facility for the generation, or transmission, or distribution of electricity.

    Structure shall be construed as though followed by the word "or part or parts of the structure and all equipment in the structure," unless the context clearly indicates otherwise.

    "Sunroom addition" means a new structure with glazing in excess of 40% of the gross area of the structure's exterior walls and roof added to an existing dwelling.

     

    R 408.30514 Means of appeal.

    Rule 514. Section R112.1 of the code is amended to read as follows:

    R112.1 Means of appeal. A person has the right to appeal a decision of the enforcing agency to the board of appeals. An application for appeal shall be based on a claim that the true intent of the code or the rules governing construction have been incorrectly interpreted, the provisions of the code do not apply, or an equal or better form of construction is proposed. The application shall be filed in accordance with section 14 of 1972 PA 230, MCL 125.1514.

    70506040

     

     

    R 408.30515 Ground snow loads.

    Rule 515. Figure R301.2(5) of the code is amended to read as follows:

     

    FIGURE R301.2(5)

     

     
    100908070706060Ground Snow Load Pg for Michigan (lb/ft2)

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    3530255020R 408.30517 Rescinded.

     

    R 408.30518 Modular ramps.

    Rule 518. Section R311.6.4 is added to the code to read as follows:

    R311.6.4 Modular ramps. Modular ramp systems approved pursuant to section 21 of 1972 PA 230, MCL 125.1521 are not required to comply with the requirements of section R403.1.4 of the code.

     

    R 408.30519 Treads and risers.

    Rule 519. Sections R311.5.3.1 and R 311.5.3.2 of the code are amended to read as follows:

    R311.5.3.1. Riser height. The maximum riser height shall be 8 1/4 inches (210 mm). The riser shall be measured vertically between leading edges of the adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm)

    R311.5.3.2. Tread depth. The minimum tread depth shall be 9 inches (229 mm). The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at a point 12 inches (305 mm) from the side where the treads are

     

     

    narrower. Winder treads shall have a minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the greatest winder tread depth at the 12-inch (305 mm) walk line shall not exceed the smallest by more than 3/8 inch (9.5 mm).

     

    R 408.30520 Doors.

    Rule 520. Section R311.4.2 of the code is amended and section R311.4.2.1 is added to the code to read as follows:

    R311.4.2. Type and size. The required exit door shall be a side-hinged door not less than 3 feet (914 mm) in width and 6 feet, 8 inches (2032 mm) in height. Other exterior hinged or sliding doors shall not be less than 24 inches in width and 6 feet, 6 inches in height.

    R311.4.2.1. Interior doors. Interior doors shall be not less than 24 inches in width and 6 feet, 6 inches in height.

    Exception: Doors to areas less than 10 square feet of floor area.

     

    R 408.30521 Elevation requirements.

    Rule 521. Section R323.2.1 of the code is amended to read as follows;

    R323.2.1. Elevation requirements. (1) Buildings and structures shall have the lowest floor elevated 1 foot above the design flood elevation.

    (2)     In areas of shallow flooding (AO zones), buildings and structures shall have the lowest floor (including basement) elevated at least as high above the highest adjacent grade as the depth number specified in feet (mm) on the FIRM, or not less than 2 feet

    (51 mm) if a depth number is not specified.

    (3)    Basement floors that are below grade on all sides shall be elevated to or above the design flood elevation.

    Exception: Enclosed areas below the design flood elevation, including basements that have floors which are not below grade on all sides, shall meet the requirements of section R323.2.2 of the code.

     

    R 408.30522 Minimum depth.

    Rule 522. Section R403.1.4 of the code is amended to read as follows:

    R403.1.4. Minimum depth. All exterior footings and foundation systems shall extend 42 inches below actual grade.

    Exceptions:

    1.   Frost-protected footings constructed in accordance with section R403.3 of the code and footings and foundations erected on solid rock shall not be required to extend below the frost line.

    2.   The footings in detached accessory structures not exceeding 400 square feet in area (37.16 m2) or 10 feet in height (3048 mm) shall extend 12 inches (305 mm) below grade to undisturbed soil or soils of sufficient bearing capacity. All vegetation and topsoil shall be removed for placement of accessory structures.

    3.   Upon evidence of the existence of any of the following conditions, the building official may modify the footing depth accordingly:

    (a)    Freezing temperatures (freezing degree days).

    (b)    Soil type.

    (c)    Ground water conditions.

    (d)    Snow depth experience.

    (e)    Exposure to the elements.

    (f)    Other specific conditions identified by the building official that may affect the foundation system.

    4.  Constructed in accordance with section R403.3.

     

     

    5.  Constructed in accordance with ASCE 32-01 as listed in chapter 43.

    6.   Decks not supported by a dwelling need not be provided with footings that extend below the frost line.

     

    R 408.30523 Rescinded.

     

    R 408.30524 Michigan uniform energy code.

    Rule 524. Buildings shall be designed and constructed in accordance with the Michigan uniform energy code part 10 rules, R 408.31001 to R 408.31099.

     

    R 408.30526 Sizing.

    Rule 526. Section M1401.3 of the code is amended to read as follows:

    M1401.3. Sizing. Heating and cooling equipment shall be sized based on building loads calculated in accordance with the provisions of ACCA Manual J-1987, as listed in chapter 43 or other approved heating and cooling calculation methodologies. Ductwork shall be sized in accordance with the provisions of ACCA Manual D-1995, as listed in chapter 43.

     

    R 408.30531 Solvent cementing.

    Rule 531. Section P2904.8.1 is added to the code to read as follows:

    P2904.8.1. Solvent cementing. Joint surfaces shall be clean and free from moisture and an approved primer shall be applied. Solvent cement, orange in color and conforming to ASTM F 493, as listed in chapter 43, shall be applied to all joint surfaces. The joint shall be made while the cement is wet and in accordance with ASTM D 2846 or ASTM F 493 as listed in chapter 43. Solvent-cement joints shall be permitted above or below ground.

    Exception: A primer is not required where all of the following conditions apply:

    a.   The solvent cement used is third-party certified as conforming to ASTM F 493 as listed in chapter 43.

    b.   The solvent cement used is yellow in color.

    c.    The solvent cement is used only for joining 1/2 inch (12.7 mm) through 2-inch (51 mm) diameter CPVC pipe and fittings.

    d.   The CPVC pipe and fittings are manufactured in accordance with ASTM D 2846 as listed in chapter 43.

     

    R 408.30534 Individual venting required.

    Rule 534. Section P3106.2 is added to the code to read as follows:

    P3106.2. Individual venting required. When fixtures other than water closets discharge into a 3-inch horizontal branch downstream from a water closet, then each fixture connected to the branch within 54 inches (1371.6 mm) downstream of the water closet flange shall be vented individually.

     

    R 408.30536 General

    Rule 536. Sections E3301.1 and E 3301.2 of the code are amended to read as follows:

    E3301.1. Applicability. The provisions of chapters 33 to 42 of the code shall establish the general scope of the electrical system and equipment requirements of the code. Chapters 33 to 42 of the code cover those wiring methods and materials most commonly encountered in the construction of 1- and 2-family dwellings and structures regulated by the code. Other wiring methods, materials, and subject matter covered in the Michigan electrical code, R 408.30801 to R 408.30880 are also allowed by the code.

    E3301.2. Scope. Chapters 33 to 42 of the code shall cover the installation of electrical systems, equipment, and components indoors and outdoors that are within the scope of the code, including

     

     

    services, power distribution systems, fixtures, appliances, devices, and appurtenances. Services within the scope of the code shall be limited to 120/240 volt, 0- to 400- ampere, single-phase systems. These chapters specifically cover the equipment, fixtures, appliances, wiring methods, and materials that are most commonly used in the construction or alteration of 1- and 2-family dwellings and accessory structures regulated by the code. The omission from these chapters of any material or method of construction provided by the Michigan electrical code, R 408.30801 to R 408.30880, shall not be construed as prohibiting the use of such material or method of construction. Electrical systems, equipment, or components not specifically covered in these chapters shall comply with the applicable provisions of the Michigan electrical code, R 408.30801 to R 408.30880.

     

    R 408.30537 Separate outdoor electric space conditioning equipment.

    Rule 537. Section E3501.6.3 is added to the code to read as follows:

    E3501.6.3. Separate outdoor electric space conditioning equipment. A service disconnect for separately metered outdoor electric space conditioning equipment may be located immediately adjacent to the outdoor meter cabinet. A permanent plaque or directory shall be installed at each service disconnect location denoting the other services, feeders, and branch circuits supplying a building or structure and area served by each service, feeder, and branch circuit.

     

    R 408.30539 Plastic pipe.

    Rule 539. Sections P3003.3.6.1 and P3003.3.6.2 are added to the code to read as follows:

    P3003.3.6.1. ABS plastic pipe. Solvent cement for ABS plastic pipe conforming to ASTM D 2235, as listed in chapter 43, shall be applied to all joint surfaces.

    P3003.3.6.2 PVC plastic pipe. A primer complying with ASTM F 656, as listed in chapter 43, shall be applied to all PVC solvent-cemented joints. Solvent cement for PVC plastic pipe conforming to ASTM D 2564, as listed in chapter 43, shall be applied to all joint surfaces.

     

    R 408.30540 Distance of trap from vent.

    Rule 540. Section P3105.1 of the code is amended to read as follows:

    P3105.1. Distance of trap from vent. Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the requirements set forth in table P3105.1.

     

    R 408.30541 Fuel burning appliances.

    Rule 541. Section M1307.6 is added to the code to read as follows:

    M1307.6. Fuel burning appliances. Fuel burning appliances shall not be installed within 10 feet (3048 mm) of a laundry chute.

     

    R 408.30542 Duct insulation/floor register location.

    Rule 542. Section M1601.3.4 of the code is amended and section M1601.3.9 is added to the code to read as follows:

    M1601.3.4. Duct insulation. Duct insulation shall be installed in accordance with the following requirements:

    1.   A vapor retarder having a maximum permeance of 0.05 perm [(2.87 ng/(s . m2 . Pa)] in accordance with ASTM E 96, as listed in chapter 43, or aluminum foil with a minimum thickness of 2 mils (0.051 mm), shall be installed on the exterior of insulation on cooling supply ducts that pass through nonconditioned spaces conducive to condensation.

    2.  Exterior duct systems shall be protected against the elements.

     

     

    3.  Duct coverings shall not penetrate a fireblocked wall or floor.

    4.   All portions of the air distribution system shall be installed in accordance with section M1601 and be insulated to an installed R-5 when system components are located within the building but outside the conditioned space, and R-8 when located outside to the building. When located within a building envelope assembly, at least R-8 shall be applied between the duct and that portion of the assembly farthest from conditioned space.

    Exception: Exhaust air ducts and portions of the air distribution system within appliances or equipment. M1601.3.9 Floor register location. Floor registers located in room or spaces containing water closets shall be located a minimum of 3 feet from the water closet.

     

    R 408.30543 Boiler low-water cutoff.

    Rule 543. Section M2002.5 of the code is amended to read as follows:

    M2002.5. Boiler low-water cutoff. All steam and hot water boilers shall be protected with a low-water cutoff control. The low-water control shall automatically stop the combustion operation of the appliance when the water level drops below the lowest safe water level as established by the manufacturer. The low-water cut off on all low-pressure boilers shall be installed in accordance with ASME code section IV which is adopted by reference in these rules. The code is available for inspection at the Michigan Department of Labor & Economic Growth, Bureau of Construction Codes and Fire Safety, 2501 Woodlake Circle, Okemos, Michigan 48864, or from the American Society of Mechanical Engineers, Three Park Avenue, New York, New York, 10016-5990, at a cost as of the time of adoption of these amendatory rules of $260.00.

    A low-water cutoff shall be of the float or probe type or paddle-type non-reversing flow switch.

     

    R 408.30544 Concrete and masonry foundation dampproofing.

    Rule 544. Section R406.1 of the code is amended to read as follows:

    R406.1. Concrete and masonry foundation dampproofing. Except where required to be waterproofed by section R406.2, foundation walls that retain earth and enclose habitable or usable spaces located below grade shall be dampproofed from the top of the footing to the finished grade. Masonry walls shall have not less than 3/8 inch (9.5 mm) Portland cement parging applied to the exterior of the wall. The parging shall be dampproofed with a bituminous coating, 3 pounds per square yard (1.63 kg/m2) of acrylic modified cement, 1/8-inch (3.2 mm) coat of surface-bonding mortar complying with ASTM C 887, as listed in chapter 43, or any material permitted for waterproofing in section R406.2. Concrete walls shall be dampproofed by applying any 1 of the above listed dampproofing materials or any 1 of the waterproofing materials listed in section R406.2 to the exterior of the wall.

    Exception: Parging of unit masonry walls is not required where a material is approved for direct application to the masonry.

     

    R 408.30545 Exterior covering.

    Rule 545. Sections R703.2, R703.6, and R703.8, and table R703.4 of the code are amended to read as follows:

    R703.2. Weather-resistive sheathing paper. A minimum of one layer of No. 15 asphalt felt complying with ASTM D 226, as listed in chapter 43, for type 1 felt or other approved weather-resistive materials shall be applied over sheathing of all exterior walls. See table R703.4. Such felt or material shall be applied horizontally, with the upper layer lapped over the lower layer not less than 2 inches (51 mm). Where joints occur, felt shall be lapped not less than 6 inches (152 mm). Building paper or other approved material shall be continuous up to the underside of the rafter or truss top chord and terminated

     

     

    at penetrations and building appendages in such a manner to meet the requirements of the exterior wall envelope as described in section R703.1.

    Exception: Such felt or material is permitted to be omitted in detached accessory buildings.

     

    Table R703.4

    WEATHER-RESISTANT SIDING ATTACHMENT AND MINIMUM THICKNESS

     

     

     

     

     

    SIDING MATERIAL

     

     

    NOMINAL THICKNESS a (INCHES)

     

     

     

     

    JOINT TREATMEN T

     

     

     

    SHEATHING PAPER REQUIRED

    TYPE OF SUPPORTS FOR THE SIDING MATERIAL AND FASTENERS bcd

    Wood or Wood Structural Panel sheathing

    Fiberboard Sheathing Into stud

    Gypsum Sheathing Into stud

    Foam Plastic Sheathin g Into stud

    Direct to studs

    Number or Spacing of fasteners

     

     

    Horizontal Aluminum

    c

    Without Insulation

    0.019f

    Lap

    Yes

    0.120 nail 1½” long

    0.120 nail 2” long

    0.120

    2” long

    0.120

    nailz

    Not allowed

    Same as stud spacing

    0.024

    Lap

    Yes

    0.120 nail 1½” long

    0.120 nail 2” long

    0.120 nail 2” long

    0.120

    nailz

    Not allowed

    With Insulation

    0.019

    Lap

    Yes

    0.120 nail 1½” long

    0.120 nail 2½” long

    0.120 nail 2½” long

    0.120

    nailz

    0.120 nail

    1½” long

    Hardboardl

    Panel siding-vertical

    7/16

    Note g

    Yes

    Note o

    Note o

    Note o

    Note o

    Note o

    6” panel edges 12” inter. Sup.p

    Hardboardl

    Lap-siding-horizontal

    7/16

    Note r

    Yes

    Note q

    Note q

    Note q

    Note q

    Note q

    Same as stud spacing

    Steeli

    29ga.

    Lap

    Yes

    0.113 nail 1¾”

    Staple-1¾”

    0.113 nail 2¾”

    Staple-2 ½”

    0.113 nail 2½” Staple- 2 ¼”

    0.113

    nailz 2½Staple

    z

    Not allowed

    Same as stud spacing

    Particleboard panels

    3/8-1/2

    Note g

    Yes

    6d box nail

    6d box nail

    6d box nail

    Box nailz

    6d box nail, 3/8 not allowed

    6” panel

    edge 12” inter.

    Sup.

    5/8

    Note g

    Yes

    6d box nail

    8d box nail

    8d box nail

    box nailz

    6d box nail

    Plywood panelj

    (exterior grade)

    3/8

    Note g

    Yes

    0.099

    nail-2”

    0.113

    nail-2½”

    0.099

    nail-2”

    0.113

    nailz Staplez

    0.099

    nail-2”

    6” on edges

    Vinyl Siding n

    0.035

    Lap

    Yes

    0.120 nail 1½” Staple- 1¾”

    0.120 nail 2”

    Staple-2½”

    0.120 nail 2”

    Staple-2½”

    .0120

    nailz Staplez

    Not allowed

    Same as stud spacing

    Wood k Rustic, drop

    3/8 Min

    Lap

    Yes

     

     

     

     

     

     

    Fastener penetration into stud-1”

    0.113

    nail-2½” Staple-2”

    Face nailing up to 6”

    widths, 1 nail per bearing; 8”

    widths and over, 2 nails per bearing

    Shiplap

    19/32

    Average

     

    Lap

     

    Yes

    Bevel

    7/16

    Butt tip

    3/16

    Lap

    Yes

    Brick veneer Concrete masonry veneer

    2

    2

    Section R703

    Yes (Note m)

    See Section R703 and Figure R703.7h

    Stone veneer

    2

    Section R703

    Yes (Note m)

    See Section R703 and Figure R703.7h

    Fiber cement panel sidings

    5/16

    Note t

    Yes

    6d corrosion resistant nailu

    6d corrosion resistant nailu

    6d corrosion resistant nailu

     

    4 d corrosion resistant nailv

    6” oc on edges, 12” oc on intermed. Studs

    Fiber cement lap sidings

    5/16

    Note w

    Yes Note y

    6d corrosion resistant nailu

    6d corrosion resistant nailu

    6d corrosion resistant nailu

     

    6d corrosion resistant nailx

    Note x

     

     

    For SI: 1" = 25.4 mm

    a.   Based on stud spacing of 16 inches on center where studs are spaced 24 inches, siding shall be applied to sheathing approved for that spacing.

    b.   Nail is a general description and shall be T-head, modified round head, or round head with smooth or deformed shanks.

    c.    Staples shall have a minimum crown width of 7/16-inch outside diameter and be manufactured of minimum 16 gage wire.

    d.   Nails or staples shall be aluminum, galvanized, or rust-preventative coated and shall be driven into the studs for fiberboard or gypsum backing.

    e.   Aluminum nails shall be used to attach aluminum siding.

    f.   Aluminum (0.019 inch) shall be unbacked only when the maximum panel width is 10 inches and the maximum flat area is 8 inches. The tolerance for aluminum siding shall be +0.002 inch of the nominal dimension.

    g.   Sheathing paper required.

    h.   All attachments shall be coated with a corrosion-resistive coating.

    i.  Shall be of approved type.

    j.    Three-eights-inch plywood shall not be applied directly to studs spaced greater than 16 inches on center when long dimension is parallel to studs. One-half-inch plywood shall not be the face grain perpendicular to the studs or over sheathing approved for that stud spacing.

    k.    Wood board sidings applied vertically shall be nailed to horizontal nailing strips or blocking set 24 inches on center. Nails shall penetrate 1.5 inches into studs, studs and wood sheathing combined, or blocking. A weather-resistant membrane shall be installed weatherboard fashion under the vertical siding unless the siding boards are lapped or battens are used.

    l.  Hardboard siding shall comply with AHA A135.6 as listed in chapter 43.

    m.     For masonry veneer, a weather-resistant sheathing paper is not required over a sheathing that performs as a weather-resistive barrier when a 1-inch air space is provided between the veneer and the sheathing. When the 1-inch space is filled with mortar, a weather-resistant sheathing paper is required over studs or sheathing.

    n.   Vinyl siding shall comply with ASTM D 3679 as listed in chapter 43.

    o.   Minimum shank diameter of 0.092 inch, minimum head diameter of 0.025 inch, and nail length shall accommodate sheathing and penetrate framing 1.5 inches.

    p.   When used to resist shear forces, the spacing must be 4 inches at panel edges and 8 inches on interior supports.

    q.   Minimum shank diameter of 0.099 inch, minimum head diameter of 0.240 inch, and nail length shall accommodate sheathing and penetrate framing 1.5 inches.

    r.   Vertical end joints shall occur at studs and shall be covered with a joint cover or shall be caulked.

    s.   Fiber cement siding shall comply with the requirements of ASTM C 1186 as listed in chapter 43.

    t.  See section R703.10.1 of the code.

    u.   Minimum 0.102 inch smooth shank, 0.255 inch round head.

    v.   Minimum 0.099 inch smooth shank, 0.250 inch round head.

    w.   See section R703.10.2 of the code.

    x.   Face nailing: 2 nails at each stud. Concealed nailing: one 11 gage 1-1/2 galvanized roofing nail (0.371 inch head diameter, 0.120 inch shank) or 6d galvanized box nail at each stud.

    y.   See exceptions in section R703.2 of the code.

    z.   Minimum nail length shall accommodate sheathing and penetrate framing 1.5 inches.

     

    R703.6. Exterior plaster. Installation of these materials shall be in compliance with ASTM C 926, which is adopted by reference in these rules and ASTM C 1063, as listed in chapter 43. The ASTM C 926

     

     

    standard is available for inspection at the Michigan Department of Labor & Economic Growth, Bureau of Construction Codes and Fire Safety, 2501 Woodlake Circle, Okemos, Michigan 48864, or from ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA, 19428, at a cost as of the time of adoption of these amendatory rules of $30.00.

    R703.6.3. Weather-resistant barriers. Weather-resistant barriers shall be installed as required in section R703.2 and, where applied over wood-based sheathing, shall include a weather-resistive vapor permeable barrier with a performance at least equivalent to 2 layers of grade D paper.

    R703.8. Flashing. Approved corrosion-resistive flashing shall be provided in the exterior wall envelope in such a manner as to prevent entry of water into the wall cavity or penetration of water to the building structural framing components. The flashing shall extend to the surface of the exterior wall finish and shall be installed to prevent water from reentering the exterior wall envelope. Flashing shall extend to, or beyond, the finished exterior face of the wall. Approved corrosion-resistive flashing shall be installed at all of the following locations:

    1.  At top of all exterior window and door openings in such a manner as to be leakproof, except that self- flashing windows having a continuous lap of not less than 1 1/8 inches (28 mm) over the sheathing material around the perimeter of the opening, including corners, do not require additional flashing; jamb flashing may also be omitted when specifically approved by the building official.

    2.    At the intersection of chimneys or other masonry construction with frame or stucco walls, with projecting lips on both sides under stucco copings.

    3.  Under and at the ends of masonry, wood, or metal copings and sills.

    4.  Continuously above all projecting wood trim.

    5.     Where exterior porches, decks, or stairs attach to a wall or floor assembly of wood-frame construction.

    6.  At wall and roof intersections.

    7.  At built-in gutters.

     

    R 408.30546 Minimum uniformly distributed live loads.

    Rule 546. Table R301.5 of the code is amended to read as follows:

     

    TABLE R301.5

    MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS

    (in pounds per square foot)

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    USE

    LIVE LOAD

    Attics with storageb

    20

    Attics without storagebg

    10

    Deckse

    40

    Exterior balconies

    60

    Fire escapes

    40

    Guardrails and handrailsd

    200

    Guardrails in-fill componentsf

    200

    Passenger vehicle garagesa

    50a

    Rooms other than sleeping rooms

    40

    Sleeping rooms

    30

    Stairs

    40c

     

     
    For SI: 1 pound per square foot = 0.0479 kN/m2, 1 square inch = 645 mm2, 1 pound = 4.45 N.

    a.   Elevated garage floors shall be capable of supporting a 2,000-pound load applied over a 20-square- inch area.

     

     

    b.   No storage with roof slope not over 3 units in 12 units.

    c.    Individual stair treads shall be designed for the uniformly distributed live load or a 300-pound concentrated load acting over an area of 4 square inches, whichever produces the greater stresses.

    d.  A single concentrated load applied in any direction at any point along the top.

    e.   See section R502.2.1 for decks attached to exterior walls.

    f.   Guard in-fill components (all those except the handrail), balusters, and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds on an area equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement.

    g.   Load shall be applied non-concurrent with other variable loads.

     

    R 408.30547. Referenced standards.

    Rule 547. The TPI standard in chapter 43 of the code is amended to update the standard to the TPI 1- 2002 edition.