9 CORRECTION OF OBVIOUS ERRORS IN PUBLICATION MEMORANDUM  

  •  

     

    DATE:            March 1, 2011

     

    TO:                 Norene Lind, Regulatory Affairs Manager

    State Office of Administrative Hearings and Rules

     

    FROM:         Deborah Young, Director

    Bureau of Construction Codes, Office of Administrative Services

     

    SUBJECT:   Request for correction of the Part 10, Michigan Uniform Energy Code R 408.31065, pursuant to Administrative Procedures Act, Section 56(1), MCL

    24.256 (1).

     

    DATE:            2010 MR 21, Eff. March 9, 2011.

     

    The Bureau of Construction Codes, as a promulgating agency, is writing to request that the State Office of Administrative Hearings and Rules exercise its discretion to correct an obvious error in the Part 10, Michigan Uniform Energy Code Rules as published in the Michigan Administrative Code.

     

    The error is contained in R 408.31065. The rule was promulgated as part of the revisions to the Part 10, Michigan Uniform Energy Code, 2010 MR 21, Eff. March 9, 2011.

     

    The agency adopted the 2009 version of the International Energy Conservation Code, amending Table 402.1.3 to reflect only Michigan specific equivalent U-factors. When the Table was typed for inclusion as the Michigan rule the anchor of footnote a was inadvertently left from the table title.

     

    The affected Table currently reads (italics added):

     

    Table 402.1.3 Equivalent U-Factors

    Climate Zone

    Fenestration

    U -Factor

    Skylight

    U -Factor

    Ceiling

    U-Factor

    Frame Wall

    U -Factor

    Mass wall

    U -Factor b

    Floor

    U -Factor

    Basement Wall

    U -Factor d

    Crawl Space Wall

    U -Factor c

    5A

    0.35

    0.60

    0.030

    0.057

    0.082

    0.033

    0.059

    0.065

    6A

    0.35

    0.60

    0.026

    0.057

    0.060

    0.033

    0.050

    0.065

    7

    0.35

    0.60

    0.026

    0.057

    0.057

    0.026

    0.050

    0.065

    a.   Nonfenestration U-factors shall be obtained from measurement, calculation, or an approved source.

    b.    When more than half the insulation is on the interior, the mass wall U-factors shall be the same as the frame wall

    U-factor in Zones 5 to 7.

    c.    Basement wall U-factor requirements shown in Table 402.1.3 include wall construction and interior air films, but exclude soil conductivity and exterior air films.

    d.    Foundation U-factor requirements shown in Table 402.1.3 include wall construction and interior air films, but exclude soil conductivity and exterior air films. U-factors for determining code compliance in accordance with

     

     

    section 402.1.4 (total UA alternative ) of section 405 (simulated performance alternative) shall be modified to include soil conductivity and exterior air films.

     

    The language should read:

     

    Table 402.1.3 Equivalent U-Factorsa

    Climate Zone

    Fenestration

    U -Factor

    Skylight

    U -Factor

    Ceiling

    U-Factor

    Frame Wall

    U -Factor

    Mass wall

    U -Factor b

    Floor

    U -Factor

    Basement Wall

    U -Factor d

    Crawl Space Wall

    U -Factor c

    5A

    0.35

    0.60

    0.030

    0.057

    0.082

    0.033

    0.059

    0.065

    6A

    0.35

    0.60

    0.026

    0.057

    0.060

    0.033

    0.050

    0.065

    7

    0.35

    0.60

    0.026

    0.057

    0.057

    0.026

    0.050

    0.065

    a.   Nonfenestration U-factors shall be obtained from measurement, calculation, or an approved source.

    b.    When more than half the insulation is on the interior, the mass wall U-factors shall be the same as the frame wall

    U-factor in Zones 5 to 7.

    c.    Basement wall U-factor requirements shown in Table 402.1.3 include wall construction and interior air films, but exclude soil conductivity and exterior air films.

    d.    Foundation U-factor requirements shown in Table 402.1.3 include wall construction and interior air films, but exclude soil conductivity and exterior air films. U-factors for determining code compliance in accordance with section 402.1.4 (total UA alternative ) of section 405 (simulated performance alternative) shall be modified to include soil conductivity and exterior air films.

     

    If you have any questions about this transmittal, you may contact me at 517.335.2626. cc: Agency Liaison, Shannon Matsumoto

     

     

     

    March 4, 2011

     

     

    Ms. Deborah Young

    Michigan Department of Energy, Labor & Economic Growth Bureau of Construction Codes

    PO Box 30255

    Lansing, MI 48909

     

    RE:  Request for correction under MCL 24.256(1) - Dear Ms. Young:

    The State Office of Administrative Hearings and Rules hereby approves your request to amend the Michigan Administrative Code under MCL 24.256(1) of the Administrative Procedures Act.

     

    Table 402.1.3 within R 408.31065 will be amended to read as follows:

     

    Table 402.1.3 Equivalent U-Factorsa

    Climate Zone

    Fenestration

    U -Factor

    Skylight

    U -Factor

    Ceiling

    U-Factor

    Frame Wall

    U -Factor

    Mass wall

    U -Factor b

    Floor

    U -Factor

    Basement Wall

    U -Factor d

    Crawl Space Wall

    U -Factor c

    5A

    0.35

    0.60

    0.030

    0.057

    0.082

    0.033

    0.059

    0.065

    6A

    0.35

    0.60

    0.026

    0.057

    0.060

    0.033

    0.050

    0.065

    7

    0.35

    0.60

    0.026

    0.057

    0.057

    0.026

    0.050

    0.065

    a.   Nonfenestration U-factors shall be obtained from measurement, calculation, or an approved source.

    b.    When more than half the insulation is on the interior, the mass wall U-factors shall be the same as the frame wall U-factor in Zones 5 to 7.

    c.    Basement wall U-factor requirements shown in Table 402.1.3 include wall construction and interior air films, but exclude soil conductivity and exterior air films.

    d.    Foundation U-factor requirements shown in Table 402.1.3 include wall construction and interior air films, but exclude soil conductivity and exterior air films.  U-factors for determining code compliance in accordance with section 402.1.4 (total UA alternative ) of section 405 (simulated performance alternative) shall be modified to include soil conductivity and exterior air films.

     

     

    MEMORANDUM

     

    DATE:            March 1, 2011

     

    TO:                 Norene Lind, Regulatory Affairs Manager

    State Office of Administrative Hearings and Rules

     

    FROM:         Deborah Young, Director

    Bureau of Construction Code, Office of Administrative Services

     

    SUBJECT:   Request for correction of the Part 10, Michigan Uniform Energy Code R 408.31060e, pursuant to Administrative Procedures Act, Section 56(1), MCL

    24.256 (1).

     

    DATE:            2010 MR 21, Eff. March 9, 2011.

     

    The Bureau of Construction Codes, as a promulgating agency, is writing to request that the State Office of Administrative Hearings and Rules exercise its discretion to correct an obvious error in the Part 10, Michigan Uniform Energy Code Rules as published in the Michigan Administrative Code.

     

    The error is contained in R 408.31060e. The rule was promulgated as part of the revisions to the Part 10, Michigan Uniform Energy Code, 2010 MR 21, Eff. March 9, 2011.

     

    The agency adopted the 2009 version of the International Energy Conversation Code, amending Table 301.3(2) to reflect only Michigan specific climate zones. When the Table was typed for inclusion as the Michigan rule the SI Units column Heating Degree Days (HDD) were incorrectly listed as Farenheit (F). This Table corresponds with Table 301.3(1), which defines the major climate types. SI Units are a metric measurement. Showing these measurements as Farenheit will create conflict and result in incorrect thermal measurements when calculating the proper insulation to be used in residential structures.

     

    The affected Table currently reads:

     

    Table 301.3(2) Climate Zone Definitions

    Zone Number

    Thermal Criteria

    IP Units

    SI Units

    5A

    5400 < HDD65°F£7200

    3000 < HDD18°F£4000

    6A

    7200 < HDD65°F£9000

    4000 < HDD18°F£5000

    7

    9000 < HDD65°F£12600

    5000 < HDD18°F£7000

    For SI: ºC = [(ºF)-32]/1.8

     

    The language should read:

     

    Table 301.3(2) Climate Zone Definitions

     

     

    Zone Number

    Thermal Criteria

    IP Units

    SI Units

    5A

    5400 < HDD65°F£7200

    3000 < HDD18°C£4000

    6A

    7200 < HDD65°F£9000

    4000 < HDD18°C£5000

    7

    9000 < HDD65°F£12600

    5000 < HDD18°C£7000

    For SI: ºC = [(ºF)-32]/1.8

     

    If you have any questions about this transmittal, you may contact me at 517.335.2626.

     

     

     

    March 4, 2011

     

     

    Ms. Deborah Young

    Michigan Department of Energy, Labor & Economic Growth Bureau of Construction Codes

    PO Box 30255

    Lansing, MI 48909

     

    RE:  Request for correction under MCL 24.256(1) Dear Ms. Young:

    The State Office of Administrative Hearings and Rules hereby approves your request to amend the Michigan Administrative Code under MCL 24.256(1) of the Administrative Procedures Act.

     

    Table 301.3(2) in R 408.31060e will be amended to read:

     

    Table 301.3(2) Climate Zone Definitions

    Zone Number

    Thermal Criteria

    IP Units

    SI Units

    5A

    5400 < HDD65°F£7200

    3000 < HDD18°C£4000

    6A

    7200 < HDD65°F£9000

    4000 < HDD18°C£5000

    7

    9000 < HDD65°F£12600

    5000 < HDD18°C£7000

    For SI: ºC = [(ºF)-32]/1.8

     

     

     

     

     