  • Section P2709.2 of the code is amended to read as follows:

    P2709.2.  Lining required.  The adjoining walls and floor framing enclosing on-site built-up shower receptors shall be lined with 1 of the following:

    1.    Sheet lead.

    2.    Sheet copper.

    3.    Plastic liner material that complies with ASTM D 4068 or ASTM D 4551.

    4.        Sheet-applied load-bearing, bonded waterproof membranes that comply with ANSI A118.10.

    The lining material shall extend not less than 3 inches (76 mm) beyond or around the rough jambs and not less than 3 inches (76 mm) above finished thresholds. Sheet- applied load bearing, bonded waterproof membranes shall be applied in accordance with the manufacturer’s instructions.