Part 5. RESIDENTIAL CODE |
Section 408.30529. Lining required.
All data is extracted from pdf, click here to view the pdf.
-
Section P2709.2 of the code is amended to read as follows:
P2709.2. Lining required. The adjoining walls and floor framing enclosing on-site built-up shower receptors shall be lined with 1 of the following:
1. Sheet lead.
2. Sheet copper.
3. Plastic liner material that complies with ASTM D 4068 or ASTM D 4551.
4. Sheet-applied load-bearing, bonded waterproof membranes that comply with ANSI A118.10.
The lining material shall extend not less than 3 inches (76 mm) beyond or around the rough jambs and not less than 3 inches (76 mm) above finished thresholds. Sheet- applied load bearing, bonded waterproof membranes shall be applied in accordance with the manufacturer’s instructions.