  • Rule 556.  Section 902.1.2 of the code is amended as follows:

    902.1.2. Elevators. Where there is an elevator or elevators for public use, at least 1 elevator serving the work area shall comply with this section. Existing elevators with a travel distance of 25 feet (7620 mm) or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire fighting or rescue purposes shall be provided with emergency operation in accordance with the Michigan elevator code. New elevators shall be provided with phase I emergency recall operation and phase II emergency in-car operation in accordance with the Michigan elevator code.