Section 325.17510. Combustion air openings.


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • (1) Nonpowered combustion air openings for fuel-fired unit space heaters, steam boilers, and water heaters shall be sized at ½ square inch of net free area per 1,000 Btu per hour input and 1 square inch net free area per 1,000 Btu per hour input for dryers.

    (2)  If powered combustion air supply equipment is used as  an     alternate to subrule

    (1)   of this rule for water heaters  and  boilers,  then  the powered combustion air supply equipment shall be selected to provide  not less  than 0.33 cubic feet per minute per 1,000 Btu per hour input and shall be electrically interlocked to the combustion controls of each unit.

History: 1981 AACS; 2004 AACS.