Section 325.21309. Patient rooms.
All data is extracted from pdf, click here to view the pdf.
-
(1) A patient bedroom shall have the floor surface at or above grade level along exterior walls with windows.
(2) A single patient room shall have not less than 80 square feet of usable floor space.
(3) A multibed patient room shall have not less than 70 square feet of usable floor space per bed.
(4) Floor area under any part of a drop or slant ceiling which is less than 7 feet, 6 inches shall not be used in computing usable floor space per patient bed.
(5) A toilet room or closet shall not be included in usable floor space.
(6) A patient room shall provide a minimum of 5 square feet of floor space per bed for wardrobe and closet, in addition to other requirements for usable floor space per bed.
(7) A bedroom shall permit the functional placement of furniture and equipment essential to patient care, comfort, and safety.
(8) A multibed patient room shall have a 3-foot clearance between beds.
(9) A patient room, toilet room, or corridor shall be provided with night lighting.
(10) A bed in a multibed patient room shall have flameproof cubicle curtains or their equivalent.
(11) A patient room shall have not less than 2 duplex electrical receptacles, at least 1 of which shall be near the head of each bed.