Section 325.21311. Patient room requirements; requirements for new construction, addition, major changes, or conversions.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • In a new construction, addition, major change, or   conversion after August 22, 1969, all of the following shall be required:

    (a)  A patient room shall have not more than 4 beds.

    (b)   A patient room shall have not less than a 3-foot clearance available on both sides and at the foot of each bed.

    (c)   An isolation room shall be a single patient room with attached lavatory, water closet, and bathing facility reserved for the use of the occupants of the isolation room only.

    (d)   A door to a patient water closet compartment shall be not less than 2 feet, 10 inches in width, and shall be equipped with suitable hardware to assure the safety of the patient.

    (e)   A single patient room shall have not less than 100 square feet of usable floor space.

    (f)   A multi-bed patient room shall have not less than 80 square feet of usable floor space per bed.

    (g)   Usable floor space shall not include a toilet room, closet, or vestibule.

    (h)   A patient room shall be provided with a lavatory and toilet room opening into the room.

History: 1981 AACS; 1983 AACS.