Section 400.4620. Interior finish.
All data is extracted from pdf, click here to view the pdf.
-
(1) The following alphabetical classification of finished materials for flame spread and smoke development, as determined by the tunnel test in accordance with the national fire protection association, standard No. 255, 2006; American society of testing materials E-84-77A, 2014; or Underwriters Laboratories standard No. 723, 2008, shall be used to determine interior finishes:
Class
Flame Spread
Smoke Developed
A
0 - 25
0 - 450
B
26 - 75
51 - 450
C
76 - 200
126 - 450
The same alphabetical classification is used for combustibility of prefabricated acoustical tile units, only under federal specifications test No. SS-5-118a.
(2) The classification of interior finish materials as to their flame spread and smoke development shall be that of the basic material used, without regard to subsequently applied paint or other coverings, except where such paint or other covering is of such a character or thickness where applied to affect the material classification. Finishes such as lacquer, polyurethane-based materials, or unapproved wall coverings shall not be used.
(3) In a newly constructed, remodeled, or converted residential group home, an interior finish classification shall be that of the basic material used, without regard to subsequently applied paint or other covering in an attempt to meet the classification.
(4) Interior finishes and materials shall be at least class C throughout.
History: 1983 AACS; 2015 AACS.