Section 400.4639. Special requirements for facilities caring for nonambulatory residents.
All data is extracted from pdf, click here to view the pdf.
-
A residential group home facility providing care to 1 or more nonambulatory residents shall comply with all of the following provisions:
(a) House such residents only on the street floor.
(b) Have required exitways which are not less than 48 inches wide in a new facility and not less than 44 inches wide in an existing or converted facility. Doors shall be a minimum of 36 inches wide.
(c) Have required exits discharge at grade level or have required exits equipped with ramps. Ramps shall not exceed 1 foot of rise in 12 feet of run and shall have sturdy handrails. Once at grade, there shall be a surface sufficient to permit occupants to move a safe distance from the facility.