Part 6. FIRE EXITS GENERAL PROVISIONS |
Section 408.10671. Fire escape stairs.
All data is extracted from pdf, click here to view the pdf.
-
(1) Fire escape stairs may be used as a required exit only in existing buildings. Fire escape stairs shall not constitute more than 50% of the required exit capacity. Fire escape stairs shall not constitute any part of the required exits for a new building.
(2) Fire escape stair dimensions shall be in accordance with table 4.
TABLE 4
Minimum Width
22 inches clear between rails
Minimum horizontal dimension of a landing or platform
22 inches
Maximum rise
9 inches
Minimum tread, exclusive of nosing
9 inches
Spiral winders
Not permitted
Maximum height between landings
12 feet
(3) Fire escape stairs shall have walls or approved guards, and handrails on both sides.