Section 408.18159. Pulverizers .  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • Rule 8159. (1) A belt drive used in connection with a pulverizer shall be grounded to remove static electricity .

    (2)    Pulverizing equipment shall be dust tight. Electrical equipment and motors located in the room or area shall be dust ignition proof, class II, division I type .

    (3)   A magnetic separator shall be installed at the material inlet to a pulverizer .

    (4)   When there are multiple pulverizers and the final pulverized material is pneumatically conveyed, each conveyor system  shall  be independent  of  the  other and electrically grounded to reduce  the likelihood of fire or explosion .

History: 1979 AC .