Section 408.30522a. Vapor retarders.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • a. Section R601.3 of the code is amended to read as follows:

    R601.3. Vapor retarders. Class I or II vapor retarders shall be provided on the interior side of frame walls in zones 5, 6, 7, 8, and marine 4.

    Exceptions:

    1.    As permitted in table R702.7.1.

    2.      Class III or no vapor retarder shall be permitted on the interior side of below grade wall assemblies. Class I or II vapor retarders shall be permitted on the interior side of the wall assembly when no air permeable insulation is installed in the below grade wall assemblies.

    3.    Construction where moisture or its freezing will not damage the materials.

History: 2008 AACS; 2010 AACS; 2015 AACS.