Section 408.30547c. General.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • Rule 547c.  Sections  N1101.3.1, N1101.7, N1101.10, N1101.12.3, N1101.16, tables

    N1101.10, and N1101.10.2(2) are amended and figure N1101.10a of the code is added to read as follows:

    N1101.3.1 (R101.4.3). Additions, alterations, renovations, or repairs. Additions, alterations, renovations, or repairs to an existing building, building system, or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portion(s) of the existing building or building system to comply with this code. Additions, alterations, renovations, or repairs shall not create an unsafe or hazardous condition or overload existing building systems. An addition shall be deemed to comply with this code if the addition alone complies or if the existing building and addition comply with this code as a single building.

    Exception:  The following are exempt provided the energy use of the building is not increased:

    1.    Storm windows installed over existing fenestration.

    2.    Glass only replacements in an existing sash and frame.

    3.      Existing ceiling, wall, or floor cavities exposed during construction provided that these cavities are filled with insulation.

    4.    Construction where the existing roof, wall, or floor cavity is not exposed.

    5.    Reroofing where the roof is part of the thermal envelope, and where neither the roof sheathing nor the roof insulation is exposed.

    6.    Reroofing where the roof is not part of the thermal envelope.

    7.       Replacement of existing doors that separate conditioned space from the exterior shall not require the installation of a vestibule or revolving door, provided, however, that an existing vestibule that separates a conditioned space from the exterior shall not be removed.

    8.      Alterations that replace less than 50% of the luminaries in a space, provided that such alterations do not increase the installed interior lighting power.

    9.     Alterations that replace only the bulb and ballast within the existing luminaries in a space provided that the alteration does not increase the installed interior lighting power.

    N1101.7 (R102.1.1). Above code programs. The state construction code commission may evaluate and approve a national, state, or local energy efficiency program to exceed the energy efficiency required by this code. Buildings approved in writing by such an energy efficiency program, such as ICC 700-2012 “silver” or energy star version 3 (rev. 07), shall be considered in compliance with this code. The requirements identified as “mandatory” in chapter 4 shall be met.

    N1101.10 (R301.1). Climate zones. Climate zones from figures 301.1, 301.1a or table

    301.1  shall be used in determining the applicable requirements of this code.

    N1101.12.3. Fenestration product rating. U-factors of fenestration products (windows, doors, and skylights) shall be determined in accordance with NFRC 100 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such a labeled U-factor shall be assigned a default U-factor from table N1101.12.3(1) or N1101.12.3(2).

    Exception: Computer simulations by independent NFRC certified laboratories or approval under section 21 of 1972 PA 230, MCL 125.1521 is considered in compliance with this section.

    N1101.16 (R401.3). Certificate (mandatory). A permanent certificate shall be posted on or in the electrical distribution panel, and shall meet all of the following:

    (a)       Be affixed or attached so it does not cover or obstruct the visibility of the circuit directory label, service disconnect label, or other required labels.

    (b)      Be completed by the builder or registered design professional.

    (c)        List the predominant R-values of insulation installed in or on ceiling/roof, walls, foundation (slab, basement wall, crawlspace wall and/or floor) and ducts outside conditioned spaces and U-factors for fenestration. If there is more than 1 value for each component, then the certificate shall list the value covering the largest area.

    (d)         List the types and efficiencies of heating, cooling, and service water heating equipment.

    (e)      If a gas-fired unvented room heater, electric furnace, or baseboard electric heater is installed in the residence, then the certificate shall list “gas-fired unvented room heater,” as appropriate. An efficiency shall not be listed for gas-fired unvented room heaters, electric furnaces, or electric baseboard heaters.

    Table N1101.10 Climate Zones by County

    Zones

    5A

    6A

    7

    Allegan

    Alcona

    Baraga

    Barry

    Alger

    Chippewa

    Bay

    Alpena

    Gogebic

    Berrien

    Antrim

    Houghton

    Branch

    Arenac

    Iron

    Calhoun

    Benzie

    Keweenaw

    Cass

    Charlevoix

    Luce

    Clinton

    Cheboygan

    Mackinac

    Eaton

    Clare

    Ontonagon

    Genesee

    Crawford

    Schoolcraft

    Gratiot

    Delta

     

    Hillsdale

    Dickinson

     

    Ingham

    Emmet

     

    Ionia

    Gladwin

     

    Jackson

    Grand Traverse

     

    Kalamazoo

    Huron

     

    Kent

    Iosco

     

    Lapeer

    Isabella

     

    Lenawee

    Kalkaska

     

    Livingston

    Lake

     

    Macomb

    Leelanau

     

    Midland

    Manistee

     

    Monroe

    Marquette

     

    Montcalm

    Mason

     

    Muskegon

    Mecosta

     

    Oakland

    Menominee

     

    Ottawa

    Missaukee

     

    Saginaw

    Montmorency

     

    Shiawassee

    Newaygo

     

    St. Clair

    Oceana

     

    St. Joseph

    Ogemaw

     

    Tuscola

    Osceola

     

    Van Buren

    Oscoda

     

    Washtenaw

    Otsego

     

    Wayne

    Presque Isle

     

     

    Roscommon

     

     

    Sanilac

     

     

    Wexford

     

    Key: A Moist. Absence of moisture designation indicates moisture regime is irrelevant.

    Table N1101.10.2(2)

    Climate Zone Definitions

    Zone Number

    Thermal Criteria

    IP Units

    SI Units

    5A

    5400 < HDD65°F£7200

    3000 < HDD18°C£4000

    6A

    7200 < HDD65°F£9000

    4000 < HDD18°C£5000

    7

    9000 < HDD65°F£12600

    5000 < HDD18°C£7000

    For SI: ºC = [(ºF)-32]/1.8

History: 2015 AACS.