Section 408.30728. Sewer depth.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • Rule 728.  Section 305.4.1 of the code is amended to read as follows:

    305.4.1. Sewer depth. A building sewer that connects to a private disposal system shall be a minimum of 8 inches (203 mm) to the top of the pipe below finished grade at the point of septic tank connection. Building sewers shall be installed a minimum of 42 inches (1067 mm) below grade.

    Exception:  When permitted by the code official.