Section 408.30870. Overcurrent protection.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • Rule 870.  Section 625.40 of the code is amended to read as follows:

    625.40     Overcurrent protection. Overcurrent protection for feeders supplying electric vehicle supply equipment shall be sized for continuous duty and shall have a rating of not less than 125% of the maximum load of the electric vehicle supply equipment. When noncontinuous loads are supplied from the same feeder, the overcurrent device shall have a rating of not less than the sum of the noncontinuous loads plus 125% of the continuous loads. The branch circuit supplying the electric vehicle equipment shall be an individual branch circuit sized for continuous duty and shall have a rating of not less than 125% of the maximum load of the electric vehicle supply equipment.

History: 1988 AACS; 1991 AACS; 1997 AACS; 2009 AACS; 2013 AACS; 2015 AACS.