Section 408.30923a. Equipment installation.
All data is extracted from pdf, click here to view the pdf.
-
Rule 923a.
Sections 301.10.1 is added to the code and section 309.1 of the code is amended to read as follows:301.10.1. Electrical disconnect. The mechanical contractor shall ensure that all equipment have an electrical disconnect switch on, or immediately adjacent to, the equipment.
309.1. Occupiable space heating system. Interior spaces intended for human occupancy shall be provided with heating facilities capable of maintaining a minimum room temperature of 68 degrees Fahrenheit at a point 3 feet above the floor and 2 feet from exterior walls at the design temperature. The installation of portable space heaters shall not be used to achieve compliance with this section.
Exception: Interior spaces where the primary purpose is not associated with human comfort.