Section 408.30945a. Ventilation; exhaust.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • a. Sections 501.3.1, 504.4, and 504.8 of the code are amended to read as follows:

    501.2.1.1 Exhaust discharge. Exhaust air shall not be directed onto walkways. Exhaust openings shall not terminate within 3 feet of a ventilated section in a soffit.

    504.4 Exhaust installation. Dryer exhaust ducts for clothes dryers shall terminate on the outside of the building, shall not terminate within 3 feet of a ventilated section in a soffit, and shall be equipped with a back draft damper. Screens shall not be installed at the duct termination. Ducts shall not be connected or installed with sheet metal screws or other fasteners that will obstruct the exhaust flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent, or chimney. Clothes dryer exhaust ducts shall not extend into or pass through ducts or plenums.

    504.8 Common exhaust systems for clothes dryers located in multistory structures. Where a common multistory duct system is designed and installed to convey exhaust from multiple clothes dryers, the system shall be engineered by a registered design professional and installed in accordance with the Michigan building codes.

History: 2003 AACS; 2007 AACS; 2010 AACS; 2013 AACS.