Section 408.30947a. Boiler connections.
Latest version.
All data is extracted from pdf, click here to view the pdf.
-
a. Section 1005.1 of the code is amended to read as follows:
1005.1 Valves. Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple boiler or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in the supply and return piping.
Exception: Shutoff valves are not required in a system having a single low-pressure steam boiler. When a boiler is located above the system and can be drained without draining the system, stop valves may be eliminated.