Section 408.31065. Equivalent U-Factors.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • Rule 1065. Section R402.1.4 and table R402.1.3 of the code are amended to read as follows:

    Table R402.1.3 Equivalent U-Factorsa

    Climate  Zone

    Fenestratio n

    U-Factor

    Skylight U-

    Factor

    Ceiling U-

    Factor

    Frame Wall U- Factor

    Mass wall U-Factor b

    Floor

    U-Factor

    Basemen tWall

    U-Factor

    Crawl Space Wall U-

    Factor

    5A

    0.32

    0.55

    0.030

    0.057

    0.082

    0.033

    0.059

    0.055

    6A

    0.32

    0.55

    0.026

    0.057

    0.060

    0.033

    0.050

    0.055

    7

    0.32

    0.55

    0.026

    0.057

    0.057

    0.028

    0.050

    0.055

    a.     Nonfenestration U-factors shall be obtained from measurement, calculation, or an approved source.

    b.      When more than half the insulation is on the interior, the mass wall U-factors shall be a maximum of 0.065 in zone 5 and marine 4, and 0.057 in zones 6 and 7.

    R402.1.4 Total UA alternative. If the total building thermal envelope UA (sum of U- factor times assembly area) is less than or equal to the total UA resulting from using the U-factors in Table R402.1.3 (multiplied by the same assembly area as in the proposed building), the building shall be considered in compliance with Table R402.1.1. The UA calculation shall be done using a method consistent with the ASHRAE Handbook of Fundamentals and shall include the thermal bridging effects of framing materials.

History: 1998-2000 AACS; 2008 AACS; 2010 AACS; 2015 AACS.