Section 408.4219. Safety valve pressure setting.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • One or more safety valves on every boiler shall be set at or below the maximum allowable working pressure. The remaining valves may be set within a range of 3% above the maximum allowable working pressure,   but the range of setting of all of the safety valves on a boiler shall not exceed 10% of the highest pressure to which any valve is set.