![]() |
Michigan Administrative Code (Last Updated: November 16, 2016) |
![]() |
Department LR. Licensing and Regulatory Affairs |
![]() |
Bureau of Construction Codes |
![]() |
Chapter Michigan Boiler Rules |
![]() |
Part 2. EXISTING INSTALLATIONS STEAM BOILERS |
Section 408.4240. Water column connections.
Latest version.
All data is extracted from pdf, click here to view the pdf.
-
No outlet connections (except for damper regulator, feedwater regulator, low-water fuel cut-out, drains, steam gauges, pressure controls or such apparatus that does not permit the escape of an appreciable amount of steam or water therefrom) shall be placed on the piping that connects the water column to the boiler. The water column shall be provided with a valved drain of at least 3/4 inches pipe size, the drain to be piped to a safe location.
History: 1979 AC.