All data is extracted from pdf, click here to view the pdf.

  • Each power boiler shall have 3 or more gauge  cocks,   located within the visible length of the water glass, except when the boiler has 2 water glasses located on the same horizontal lines. Boilers not over 36 inches in diameter, in which the heating  surface  does  not  exceed   100 square feet, need have but 2 gauge cocks. For all installations  where   the water gauge glass or glasses are   more  than  30  feet  above the boiler operating floor, it is recommended  that   water-level  indicating  or recording gauges be installed at eye height above the operating floor.