Pipe connections, if threaded, shall be tapped into material having a minimum thickness as specified in table HG-370, except that when a curved surface is to be tapped the minimum thickness shall be sufficient to permit at least 4 full threads to be engaged.
TABLE HG-370
MINIMUM THICKNESS OF MATERIAL FOR THREADED CONNECTIONS TO BOILERS
Size of Pipe Connection, Minimum Thickness of Material Inches Required, Inches Under 3/4 1/4 3/4 to 1, inclusive
5/16 1 1/4 to 2 1/2, inclusive 7/16 3 to 3 1/2,
inclusive 5/8 4 to 5, inclusive
7/8 6 to 8, inclusive
1 9 to 12, inclusive 1 1/4
History: 1954 ACS 49, Eff. Feb. 14, 1967; 1979 AC.