Section 408.4265. Minimum distance required between boiler and floor.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • Boilers other than cast iron of the wet-bottom type having an external width of over 36 inches shall  have   not  less  than   12  inches between the bottom of the boiler and  the  floor  line, with  access   for inspection. When the width is 36 inches or less, the distance between the bottom of the boiler and the floor line shall be not less than 6 inches and when any part of the wet bottom is not farther from an outer edge than 12 inches, it shall be not less than 4 inches.