Section 408.4272. Minimum capacity of closed-type tank.
All data is extracted from pdf, click here to view the pdf.
-
The minimum capacity of the closed-type expansion tank may be determined from tables 272A and 272B or from the following formula where the necessary information is available.
Vt = (0.00041 T-).0466Vs
Pa - Pa Pf - Po
Where: Vt = minimum volume of tanks, gallons
Vs = volume of system, not including tanks, gallons
T = average operating temperature, degrees Fahrenheit Pa = atmospheric pressure, psia
Pf = fill pressure, psia
Po = maximum operating pressure, psia
Table 272A
Expansion Tank Capacity for Gravity Hot Water Systems Based on 2-pipe system with average operating water temperature 170 degrees Faherenheit, using cast iron column radiation with heat emission rate 150 Btu per hour square foot equivaelnt direct radiation.
Square Feet of Installed Tank Capacity Equivalent Direct Radiation 1 Gallons
Up to 350
18
Up to 450
21
Up to 650
24
Up to 900
30
Up to 1,100
35
Up to 1,400
40
Up to 1,600
2 - 30
Up to 1,800
2 - 30
Up to 2,000
2 - 35
Up to 2,400
2 - 40
1 For systems with more than 2,400 square feet of installed equivalent direct water radiation, the required capacity of the cushion tank shall be increased on the basis of 1 gallon tank capacity per 33 square feet of additional equivalent direct radiation.
Table 272B
Expansion Tank Capacities for Forced Hot Water Systems Based on average operating water temperature 195 degrees Fahrenheit, a fill pressure 12 psig and maximum operating pressure 30 psig.
System Volume, Gallons 1 Tank Capacity, Gallons
100
15
200
30
300
45
400
60
500
75
1,000
150
2,000
300
1 Includes volume water in boiler, radiation, and piping, not including expansion tank.
History: 1979 AC.