Section 408.7026. Disconnecting means for new and altered elevators.
Latest version.
All data is extracted from pdf, click here to view the pdf.
-
The disconnecting means for all elevators and escalators that have 208 volts alternating current (VAC) nominal, shall be a heavy-duty type means and feature a dual cover interlock or a circuit breaker capable of being locked in the open position.
History: 2003 AACS; 2014 AACS.