Michigan Administrative Code (Last Updated: November 16, 2016) |
Department LR. Licensing and Regulatory Affairs |
Public Service Commission |
Chapter Technical Standards For Gas Service |
Part 5. INSPECTION OF METERS |
Section 460.2354. Accuracy of metering equipment; tests; standards.
All data is extracted from pdf, click here to view the pdf.
-
(1) The utility shall use the applicable provisions of the standards listed in R 460.2342 as criteria of accepted practice in testing meters.
(2) Metering equipment shall be tested by comparison with the standards that are referenced in R 460.2342.
(3) A gas service meter that is repaired or removed from service for any cause shall, before installation, be tested and adjusted to be correct within 1% fast or 1% slow.
(4) Every diaphragm-type gas meter shall be tested before installation and adjusted, if required, to a meter accuracy of 100% plus or minus 1% at a low flow rate and at a high flow rate so that the numerical difference between the meter accuracy at these 2 flow rates is not more than 1 percentage point. A low flow rate is a flow at 20% to 50% of the rated capacity of the meter. A high flow rate is a flow at 80% to 120% of the rated capacity of the meter. The average meter accuracy of a
diaphragm-type meter shall be defined as 1/2 the sum of the meter accuracy at the low flow test and at the high flow test.
(5) All recording-type meters or associated instruments that have a timing element that serves to record the time at which the measurement occurs for billing purposes shall be adjusted at intervals of not more than 2 years so that the timing element is not in error by more than plus or minus 4 minutes in 24 hours, under laboratory conditions, as set forth in ANSI B109.1 (which is adopted by reference in R 460.2342(b)(ii)), or by more than plus or minus 10 minutes in 24 hours under field conditions.
History: 1979 AC; 1993 AACS.