Section 460.2381. Gas purity.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • (1) Gas that is distributed by a utility to a customer shall not contain more than 0.3 grains of hydrogen sulfide  or  more   than  20 grains of total sulfur per 100 cubic feet, including the   sulfur  in   any hydrogen sulfide.

    (2) Gas that is distributed by a utility to a customer shall not contain flammable liquids in quantities that interfere with the normal operation of the customer's equipment.

History: 1979 AC; 1993 AACS.