Section 460.3610. Portable indicating voltmeters; accuracy.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  •  All  portable  indicating   voltmeters  that   are  used   for determining the quality of service voltage to customers shall be checked against a suitable secondary reference standard at least once every 6 months for analog devices, and once every 12 months  for  digital  devices.  The accuracy of these voltmeters  shall   be  rated so that the error of  the indication is not more than plus or minus 1% of full scale. If the portable indicating voltmeter is found to be in error by more than the rated accuracy at commonly used scale deflections, it shall be adjusted.

History: 1983 AACS; 2008 AACS.