Michigan Administrative Code (Last Updated: November 16, 2016) |
![]() |
Department LR. Licensing and Regulatory Affairs |
![]() |
Public Service Commission |
![]() |
Chapter Technical Standards for Electric Service |
![]() |
Part 6. METERING EQUIPMENT INSPECTIONS AND TESTS |
Section 460.3610. Portable indicating voltmeters; accuracy.
Latest version.
All data is extracted from pdf, click here to view the pdf.
-
All portable indicating voltmeters that are used for determining the quality of service voltage to customers shall be checked against a suitable secondary reference standard at least once every 6 months for analog devices, and once every 12 months for digital devices. The accuracy of these voltmeters shall be rated so that the error of the indication is not more than plus or minus 1% of full scale. If the portable indicating voltmeter is found to be in error by more than the rated accuracy at commonly used scale deflections, it shall be adjusted.
History: 1983 AACS; 2008 AACS.