Section 460.722. Unacceptable levels of performance during service interruptions.
All data is extracted from pdf, click here to view the pdf.
-
It is an unacceptable level of performance for an electric utility to fail to meet any of the following service interruption standards:
(a) Considering data derived through the amalgamation of data from both normal and catastrophic conditions, an electric utility shall restore service within 36 hours to not less than 90% of its customers experiencing service interruptions.
(b) Considering data including only catastrophic conditions, an electric utility shall restore service within 60 hours to not less than 90% of its customers experiencing service interruptions.
(c) Considering data including only normal conditions, an electric utility shall restore service within 8 hours to not less than 90% of its customers experiencing service interruptions.
(d) Considering data derived through the amalgamation of data from both normal and catastrophic conditions, an electric utility shall not experience 5 or more same circuit repetitive interruptions in a 12-month period on more than 5% of its circuits.