4 Rule 516. Table R301.2(1) of the code is amended and figures R301.2(7) and R301.2(8) are added to the code to read as follows:
-
TABLE R 301.2(1)
CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
Ground
Snow Load
Wind Speed
d
(mph)
Seismic Design Categor yf
Subject to Damage From
Winte r Desig n Tempe
Ice Barrier Underla yment
Require dh
Flood Hazar dsg
Air Freezin g Indexi
Mean Annual Tempj
Weatheri nga
Frostlin e depthb
Termi tec
See Note e
Yes
See Note g
Figure R403.3( 2)
See footnote J
Figure R301.2(5)
90
See Sec.R30 1.2.2.1
& Figure R301.2( 2)
Severe
42” See Note b
Figure R301. 2(6)
For SI: 1 pound per square foot = 0.0479 kN/m2, 1 mile per hour = 1.609 km/h.
a. Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements of this code. The weathering column shall be filled in with the weathering index (i.e., “negligible”, “moderate” or “severe”) for concrete as determined from the weathering probability map [figure R301.2(3)]. The grade of masonry units shall be determined from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C 652 as listed in chapter 43.
b. The frost line depth may be modified as provided in section R403.1.4 of the code.
c. The jurisdiction shall fill in this part of the table to indicate the need for protection depending on whether there has been a history of local damage.
d. The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [figure R301.2(4)]. Wind exposure category shall be determined on a site-specific basis in accordance with section R301.2.1.4 of the code.
e. The winter design temperature criteria shall be taken from appendix D of the Michigan plumbing code, R 408.30701 to R 408.30796.
f. Design category determined from section R301.2.2.1 of the code.
g. The jurisdiction shall fill in this part of the table with (a) the date of the jurisdiction’s entry into the national flood insurance program (date of adoption of the first code or ordinance for management of flood hazard areas), (b) the date(s) of the currently effective FIRM and FBFM or other flood hazard map adopted by the community, as may be amended. Absent (a) or (b), flood hazard areas as determined by the state under its administration of the Part 31, floodplain regulatory authority of the natural resources and environmental protection act, 1994 PA 451, MCL 324.101 to 324.90106, shall become the basis for regulation of floodplain development within the community and section R324 of the code shall apply to buildings and structures within those areas
h. In accordance with sections R905.2.7.1, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and R905.8.3.1 of the code, for areas where the average daily temperature in January is 25 degrees Fahrenheit (-4 degrees Celsius) or less, or where there has been a history of local damage from the
effects of ice damming, the jurisdiction shall fill in this part of the table with “YES”. Otherwise, the jurisdiction shall fill in this part of the table with “NO”.
i. The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (bf-days) from figure R403.3(2) or from the 100-year (99%) value on the national climatic data center data table “air freezing index- USA method (base 32 degrees Fahrenheit)”.
j. The jurisdiction shall fill in this part of the table with the mean annual temperature from the national climatic data center data table “air freezing index-USA method (base 32 degrees Fahrenheit)” at www.ncdc.noaa.gov/fpsf.html.
R 408.30518 Means of egress
Modular ramps.Rule 518. Sections R311.6.4 and R311.4.2.1 are
isadded to the code and R311.4.2 of the code is amended to read as follows:R311.6.4 Modular ramps. Modular ramp systems approved pursuant to
section 21 of 1972 PA 230,MCL125.1521the act are not required to comply with the requirements of section R403.1.4 of the code. R311.4.2. Door type and size. The required exit door shall be a side-hinged door not less than 3 feet (914 mm) in width and 6 feet, 8 inches (2032 mm) in height. Other exterior hinged or sliding doors shall not be less than 24 inches in width and 6 feet, 6 inches in height.R311.4.2.1. Interior doors. Interior doors shall be not less than 24 inches in width and 6 feet, 6 inches in height.
Exception: Doors to areas less than 10 square feet of floor area.
R 408.30520
Doors.Wood wall framing.Rule 520. Section
R311.4.2R602.10.5 of the code is amendedandsection R311.4.2.1 is added to thecodeto read as follows:R311.4.2. Type and size. The required exit door shall be a side-hinged door not less than 3 feet (914mm) in width and 6 feet, 8 inches (2032 mm) in height. Other exterior hinged or sliding doors shall notbe less than 24 inches in width and 6 feet, 6 inches in height.R311.4.2.1. Interior doors. Interior doors shall be not less than 24 inches in width and 6 feet, 6 inchesin height.Exception: Doors to areas less than 10 square feet of floor area.R602.10.5. Continuous structural panel sheathing. When continuous wood structural panel sheathing is provided in accordance with method 3 of R602.10.3 of the code, including areas above and below openings, braced wall panel lengths shall be in accordance with table R602.10.5 of the code. Wood structural panel sheathing shall be installed at corners in accordance with figure R602.10.5 of the code. The bracing amounts in table R602.10.1 of the code for method 3 shall be permitted to be multiplied by a factor of 0.9 for walls with a maximum opening height that does not exceed 85% of the wall height or a factor of 0.8 for walls with a maximum opening height that does not exceed 67% of the wall height.
R 408.30521 Elevation requirements.
Rule 521. Section
R3234.2.1 of the code is amended to read as follows;R3234.2.1. Elevation requirements. (1)Buildings and structures shall have the lowest floor elevated1 foot above the design flood elevation.Buildings and structures shall have the lowest floor including basements elevated so the lowest point of the floor’s concrete or subfloor surface is 1 foot (305 mm) or more above the design flood elevation. The bottom of the lowest horizontal structural member of the floor system shall not be lower than the design flood elevation.Compliance with this elevation requirement shall be based upon measurement taken from the
floor surface without the final floor covering and from the bottom of the lowest horizontal structural member of the floor system.
(2)
In areas of shallow flooding (AO zones), buildings and structures shall have the lowest floor(including basement) elevated at least as high above the highest adjacent grade as the depth numberspecified in feet (mm) on the FIRM, or not less than 2 feet(51 mm) if a depth number is not specified.Crawl space interior floor grade elevation shall comply with R408.6 of the code.(3)
Basement floors that are below grade on all sides shall be elevated to or above the design floodelevation.Basement floors that are below grade on all sides shall be considered lowest floors and shall be elevated so that the lowest point of the floor surface is 1 foot (305 mm) or more above the design flood elevation. Compliance with this elevation requirement shall be based upon measurement taken from the floor surface without the final floor covering.Exception: Enclosed areas below the design flood elevation, including basements that have floors which are not below grade on all sides, shall meet the requirements of section
R3234.2.2 of the code.R 408.30522 Minimum depth.
Rule 522. Section R403.1.4 of the code is amended to read as follows:
R403.1.4. Minimum depth. All exterior footings and foundation systems shall extend 42 inches below actual grade. Where applicable, the depth of the footings shall also conform to sections R403.1.4.1 to R403.1.4.2 of the code.
Exceptions:1. Frost-protected footings constructed in accordance with section R403.3 of the code and footings andfoundations erected on solid rock shall not be required to extend below the frost line.2. The footings in detached accessory structures not exceeding 400 square feet in area (37.16 m2
) or 10feet in height (3048 mm) shall extend 12 inches (305 mm) below grade to undisturbed soil or soils ofsufficient bearing capacity. All vegetation and topsoil shall be removed for placement of accessorystructures.3.Upon evidence of the existence of any of the following conditions, the building official may modify the footing depth accordingly:(a) Freezing temperatures (freezing degree days).
(b) Soil type.
(c) Ground water conditions.
(d) Snow depth experience.
(e) Exposure to the elements.
(f) Other specific conditions identified by the building official that may affect the foundation system.
4. Constructed in accordance with section R403.3.5. Constructed in accordance with ASCE 32-01 as listed in chapter 43.6. Decks not supported by a dwelling need not be provided with footings that extend below the frostline.R 408.30525 Scope.
Rule 525. Section M1301.1 of the code is amended to read as follows:
M1301.1. Scope. The provisions of this chapter shall govern the installation of mechanical systems not specifically covered in other chapters applicable to mechanical systems. Installations of mechanical appliances, equipment, and systems not addressed by the code shall comply with the applicable provisions of the Michigan mechanical code, R
408.30901a to R408.30998a and the international fuel gas codelisted in chapter 43.R 408.30526 Sizing.
Rule 526. Section M1401.3 of the code is amended to read as follows:
M1401.3. Sizing. Heating and cooling equipment shall be sized in accordance with ANSI/ACCA manual S 3-2004, as listed in chapter 43, based on building loads calculated in accordance with the provisions of ACCA Manual J-1987, as listed in chapter 43 or other approved heating and cooling calculation methodologies. Ductwork shall be sized in accordance with the provisions of ACCA Manual D-1995, as listed in chapter 43.
R 408.30528 Terms defined in other codes.
Rule 528. Section G2402.3 of the code is amended to read as follows:
G2402.3. Terms defined in other codes. Where terms are not defined in the code and are defined in the Michigan electrical code, R 408.30801 to R 408.30880, Michigan building code, R 408.30401 to R
408.30499a547, international fire code listed in chapter 43, Michigan mechanical code, R408.30901a to R408.30998a or Michigan plumbing code, R 408.30701 to R 408.30796, the terms shall have the meanings ascribed to them as in those codes.R 408.30529 Lining required.
Rule 529. Section P2709.2 of the code is amended as follows:
P2709.2. Lining required. The adjoining walls and floor framing enclosing on-site built-up shower receptors shall be lined with sheet lead, copper, or a plastic liner material that complies with ASTM D 4068 or ASTM D 4551 listed in chapter 43. The lining material shall extend not less than 3 inches (76 mm) beyond or around the rough jambs and not less than 3 inches (76 mm) above the finished thresholds.
R 408.30530
Relief valve dischargeRequirements for discharge pipe. Rule 530. Section P2803.6.1 of the code is amended to read as follows:P2803.6.1.
Relief valve dischargeRequirements for discharge pipe.Relief valve discharge pipesshall be rigid pipe approved for water distribution with a rating of 210 degrees Fahrenheit. Thedischarge pipe shall be the same diameter as the relief valve outlet and shall drain by gravity flow.Valves shall not be connected in the relief valve discharge pipe. Relief valves shall not discharge so asto be a hazard, a potential cause of damage, or a nuisance. Discharge pipe from relief valves shallterminate atmospherically not more than 4 inches from the floor with an unthreaded end and shall not bedirectly connected to the drainage system.Relief valves shall not discharge so as to be a hazard, a potential cause of damage, or a nuisance. A relief valve discharge pipe shall be provided for each individual relief valve and shall meet all of the following:a. Shall terminate atmospherically not more than 4 inches (102 mm) from the floor with an unthreaded end.
b. Shall not be interconnected.
c. Valves shall not be connected in the relief valve discharge pipe.
d. Shall be rigid pipe approved for water distribution, with a minimum temperature rating of 210 degrees Fahrenheit.
e. Shall have the same nominal inside diameter as the relief valve outlet and shall drain by gravity flow.
The outlet of a pressure, temperature, or other relief valve shall not be directly connected to the drainage system.
R 408.30531
Solvent cementing.Rule 531. Section P2904.8.1 is added to the code to read as follows:P2904.8.1. Solvent cementing. Joint surfaces shall be clean and free from moisture and an approvedprimer shall be applied. Solvent cement, orange in color and conforming to ASTM F 493, as listed inchapter 43, shall be applied to all joint surfaces. The joint shall be made while the cement is wet and inaccordance with ASTM D 2846 or ASTM F 493 as listed in chapter 43. Solvent-cement joints shall bepermitted above or below ground.Exception: A primer is not required where all of the following conditions apply:a. The solvent cement used is third-party certified as conforming to ASTM F 493 as listed in chapter43.b. The solvent cement used is yellow in color.c. The solvent cement is used only for joining 1/2 inch (12.7 mm) through 2-inch (51 mm) diameterCPVC pipe and fittings.d. The CPVC pipe and fittings are manufactured in accordance with ASTM D 2846 as listed in chapter43.Duct construction.Rule 531. Section M1601.3.1 of the code is amended to read as follows:
M1601.3.1. Joints and seams. Joints of duct systems shall be made substantially airtight by means of tapes, mastics, gasketing, cleats, or other approved closure systems. Joints of duct systems located outside the building thermal envelope shall be made airtight by means of tapes, mastics, caulk, gasketing, or other approved sealants. Closure systems used with rigid fibrous glass ducts shall comply with UL 181A and shall be marked “181A-P” for pressure-sensitive tape, “181A-M” for mastic or “181A-H” for heat-sensitive tape. Closure systems sued with flexible air ducts and flexible air connectors shall comply with UL 181B and shall be marked “181B-FX” for pressure-sensitive tape or “181B-M” for mastic. Duct connections to flanges of air distribution system equipment or sheet metal fittings shall be mechanically fastened. Mechanical fasteners for use with flexible nonmetallic air ducts shall comply with UL 181B and shall be marked 181B-C. Crimp joints for round ducts shall have a contact lap of at least 1.5 inches (38 mm) and shall be mechanically fastened by means of at least 3 sheet metal screws or rivets spaced around the joint.
R 408.30534
Individual venting required.Venting.Rule 534. Section P3105.1 and tables 3002.1 (1), 3002.1 (2) and 3002.2 are amended and section 3105.4
P3106.2and figure 3105.4isare added to the codeto readand figure N3 in appendix N of the code is amended to read as follows:P3105.1. Distance of trap from vent. Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the requirements set forth in table P3105.1 of the code.
P3106.2. Individual venting required. When fixtures other than water closets discharge into a 3-inchhorizontal branch downstream from a water closet, then each fixture connected to the branch within 54inches (1371.6 mm) downstream of the water closet flange shall be vented individually.P3105.4.Vertical leg for waste fixture drains. A vertical leg (see figure P3105.4) is permitted within a fixture drain of a waste fixture in accordance with the following criteria:
1. Minimum trap diameter shall be in accordance with table P3201.7 of the code.
2. The diameter of section A shall be equal to the diameter of the trap.
3. The length of section A shall not be less than 8 inches (203 mm) and in accordance with table P3105.1 of the code.
4. The diameter of section B shall be 1 pipe size larger than the diameter of Section A.
5. The length of section B shall not be more than 36 inches (914 mm).
6. The diameter of section C shall be 1 pipe size larger than the diameter of section B.
7. The total length of section A and section C shall not exceed the distance allowed in table P3105.1 of the code.
8. Bends shall be the diameter of the largest connected section.
Figure N3. Typical horizontal wet venting.
TABLE P3002.1 (1)
ABOVE-GROUND DRAINAGE AND VENT PIPE
MATERIAL
STANDARD
Acrylonitrile butadiene styrene (ABS) plastic pipe
ASTM D 2661; ASTM F 628; CSA B 181.1
Brass pipe
ASTM B 43
Cast-iron pipe
ASTM A 74; CISPI 301; ASTM A 888
Coextruded composite ABS DWV schedule 40 IPS pipe (solid)
ASTM F 1488
Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core)
ASTM F 1488
Coextruded composite PVC DWV schedule 40 IPS pipe (solid)
ASTM F 1488
Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core)
ASTM F 1488; ASTM F 891
Coextruded composite ABS IPS-DR, PS140, PS200 DWV
ASTM F 1488
Coextruded composite PVC IPS-DR, PS140, PS200 DWV
ASTM F 1488
Copper or copper-alloy pipe
ASTM B 42; ASTM B 302
Copper or copper-alloy tubing (Type K, L, M or DWV)
ASTM B 75; ASTM B 88; ASTM B 251;
ASTM B 306
Galvanized steel pipe
ASTM A 53
Polyolefin pipe
CSA B181.3
Polyvinyl chloride (PVC) plastic pipe (Type DWV)
ASTM D 2665; ASTM D 2949; CSA B181.2; ASTM F 1488
Stainless steel drainage systems, Types 304 and 316L
ASME A112.3.1
TABLE P3002.1(2)
UNDERGROUND BUILDING DRAINAGE AND VENT PIPE
MATERIAL
STANDARD
Acrylonitrile butadiene styrene (ABS) plastic pipe
ASTM D 2661; ASTM F 628; CSA B181.1
Asbestos-cement pipe
ASTM C 428
Cast-iron pipe
ASTM A 74; CISPI 301; ASTM A 888
Coextrueded composite ABS DWV schedule 40 IPS pipe (solid)
ASTM F 1488
Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core)
ASTM F 1488
Coextruded composite PVC DWV schedule 40 IPS pipe (solid)
ASTM F 1488
Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core)
ASTM F 891; ASTM F 1488
Coextruded composite ABS IPS-DR, PS140, PS200 DWV
ASTM F 1488
Coextruded composite PVC IPS-DR, PS140, PS200 DWV
ASTM F 1488
Copper or copper alloy tubing (Type K, L, M or DWV)
ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 306
Polyolefin pipe
ASTM F 1412; CSA B181.3
Polyvinyl chloride (PVC) plastic pipe (Type DWV)
ASTM D 2665; ASTM D 2949; CSA B181.2
Stainless steel drainage systems, Type 316L
ASME A112.3.1
TABLE P3002.2 BUILDING SEWER PIPE
MATERIAL
STANDARD
Acrylonitrile butadiene styrene (ABS) plastic pipe
ASTM D 2661; ASTM D 2751; ASTM F 628
Asbestos-cement pipe
ASTM C 428
Cast-iron pipe
ASTM A 74; ASTM A 888; CISPI 301
Coextruded composite ABS DWV schedule 40 IPS pipe (solid)
ASTM F 1488
Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core)
ASTM F 1488
Coextruded composite PVC DWV schedule 40 IPS pipe (solid)
ASTM F 1488
Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core)
ASTM F 1488; ASTM F 891
Coextruded composite ABS IPS-DR-PS DWV, PS140, PS200
ASTM F 1488
Coextruded composite PVC IPS-DR-PS DWV, PS140, PS200
ASTM F 1488
Coextruded composite ABS sewer and drain DR-PS in PS35, PS50, PS100, PS140, PS200
ASTM F 1488
Coextruded composite PVC sewer and drain DR-PS in PS35, PS50, PS100, PS140, PS200
ASTM F 1488
Coextruded composite PVC sewer and drain PS 25, PS 50, PS 100 (cellular core)
ASTM F 891
Concrete pipe
ASTM C 14; ASTM C 76; CSA A 257.1M; CSA A 257.2M
Copper or copper-alloy tubing (Type K or L)
ASTM B 75; ASTM B 88; ASTM B 251
Polyethylene (PE) plastic pipe (SDR-PR)
ASTM F 714
Polyolefin pipe
ASTM F 1412; CSA B181.3
Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR 26, SRD35, SDR41, PS50 or PS100)
ASTM D 2665; ASTM D 2949; ASTM D 3034; ASTM F 1412; CSA B182.2; CSA B182.4
Stainless steel drainage systems, Types 304 and 316L
ASME A112.3.1
Vitrified clay pipe
ASTM C 425; ASTM C 700
R 408.30536
GeneralElectrical, general, electrical conductors and connections and electrical grounding.Rule 536. Sections E3301.1,
andE 3301.2, E3306.7, E3808.8.1, E3808.8.2, and table E3502.2 of the code are amended to read as follows:E3301.1. Applicability. The provisions of chapters 33 to 42 of the code shall establish the general scope of the electrical system and equipment requirements of the code. Chapters 33 to 42 of the code cover those wiring methods and materials most commonly encountered in the construction of 1- and 2- family dwellings and structures regulated by the code. Other wiring methods, materials, and subject matter covered in the Michigan electrical code, R 408.30801 to R 408.30880 are also allowed by the code.
E3301.2. Scope. Chapters 33 to 42 of the code shall cover the installation of electrical systems, equipment, and components indoors and outdoors that are within the scope of the code, including services, power distribution systems, fixtures, appliances, devices, and appurtenances. Services within the scope of the code shall be limited to 120/240 volt, 0- to 400- ampere, single-phase systems. These chapters specifically cover the equipment, fixtures, appliances, wiring methods, and materials that are most commonly used in the construction or alteration of 1- and 2-family dwellings and accessory structures regulated by the code. The omission from these chapters of any material or method of construction provided by the Michigan electrical code, R 408.30801 to R 408.30880, shall not be
construed as prohibiting the use of such material or method of construction. Electrical systems, equipment, or components not specifically covered in these chapters shall comply with the applicable provisions of the Michigan electrical code, R 408.30801 to R 408.30880.
E3306.7. Conductors of the same circuit. All conductors of the same circuit and, where used, the grounded conductor and all equipment grounding conductors shall be contained within the same raceway, cable, trench or cord.
TABLE E3502.2
MINIMUM SERVICE LOAD CALCULATION
LOADS AND PROCEDURE
3 volt-amperes per square foot of floor area for general lighting and general use receptacle outlets.
Plus
1,500 volt-amperes total number of 20- ampere-rated small appliance and laundry circuits.
Plus
The nameplate volt-ampere rating of all fastened-in-place, permanently connected or dedicated circuit-supplied motors and appliances such as ranges, ovens, cooking units, clothes dryers, and water
heaters.
Apply the following demand factors to the above subtotal:
The minimum subtotal for the loads above shall be 100% of the first 10,000 volt-amperes of the sum of the above loads plus 40% of any portion of the sum that is in excess of 10,000 volt-amperes.
Plus the largest of the following:
Nameplate rating(s) of the air-conditioning and cooling equipment.
Nameplate rating(s) of the heating where a heat pump is used without any supplemental electric heating.
Nameplate rating of the electric thermal storage and other heating systems where the usual load is expected to be continuous at the full nameplate value. Systems qualifying under this selection shall not be figured under any other category in this table.
One hundred percent of nameplate rating of the heat pump compressor and 65 percent of the supplemental electric heating load for
central electric space-heating systems. If the heat pump compressor is prevented from operating at the same time as the supplementary heat, the compressor load does not need to be added to the supplementary heat load for the total central electric space-heating load.
Sixty-five percent of nameplate rating(s) of electric space-heating units if less than 4 separately controlled units.
Forty percent of nameplate rating(s) of electric space-heating units of 4 or more separately controlled units.
The minimum total load in amperes shall be the volt-ampere sum calculated above divided by 240 volts.
E3808.8.1. Grounding of flexible metal conduit. Flexible metal conduit shall not be permitted as an equipment grounding conductor.
E3808.8.2. Grounding of liquid-tight flexible metal conduit. Liquid-tight flexible metal conduit shall not be permitted as an equipment grounding conductor.
R 408.30539
Plastic pipeSolvent cementing.Rule 539.
SectionsP3003.3.6.1 and P3003.3.6.2P3003.14.2are added toof the code is amended to read as follows:P3003.3.6.1. ABS plastic pipe. Solvent cement for ABS plastic pipe conforming to ASTM D 2235, aslisted in chapter 43, shall be applied to all joint surfaces.P3003.3.6.2 PVC plastic pipe. A primer complying with ASTM F 656, as listed in chapter 43, shall beapplied to all PVC solvent-cemented joints. Solvent cement for PVC plastic pipe conforming to ASTMD 2564, as listed in chapter 43, shall be applied to all joint surfaces.P3003.14.2 Solvent cementing.Joint surfaces shall be clean and free from moisture. A primer that conforms to ASTM F 656, as listed in chapter 43, shall be applied. Solvent cement not purple in color and conforming to ASTM D 2564, CSA B137.3 or CSA B181.2, as listed in chapter 43, shall be applied to all joint surfaces. The joint shall be made while the cement is wet, and shall be in accordance with ASTM D 2855, as listed in chapter 43. Solvent-cement joints shall be permitted above or below ground.
R 408.30540
Distance of trap from vent.Elevators and platform lifts.Rule 540. Sections R323.1 and R323.2
P3105.1of the codeisare amended to read as follows:P3105.1. Distance of trap from vent. Each fixture trap shall have a protecting vent located so that theslope and the developed length in the fixture drain from the trap weir to the vent fitting are within therequirements set forth in table P3105.1.R323.1. Elevators. Where provided, passenger elevators, limited-use/limited-application elevators or private residence elevators shall comply with the Michigan elevator rules R 408.7001 to R 408.8695.
R323.2. Platform lifts. Where provided, platform lifts shall comply with the Michigan elevator rules, R 408.7001 to R 408.8695.
R 408.30543 Boiler low-water cutoff.
Rule 543. Section M2002.5 of the code is amended to read as follows:
M2002.5. Boiler low-water cutoff. All steam and hot water boilers shall be protected with a low-water cutoff control. The low-water control shall automatically stop the combustion operation of the appliance when the water level drops below the lowest safe water level as established by the manufacturer. The low-water cut off on all low-pressure boilers shall be installed in accordance with the Michigan boiler rules, R 408.4001 to R 408.5507.
ASME code section IV which is adopted byreference in these rules. The code is available for inspection at the Michigan Department of Labor &Economic Growth, Bureau of Construction Codes and Fire Safety, 2501 Woodlake Circle, Okemos,Michigan 48864, or from the American Society of Mechanical Engineers, Three Park Avenue, NewYork, New York, 10016-5990, at a cost as of the time of adoption of these amendatory rules of $260.00.A low-water cutoff shall be of the float or probe type or paddle-type non-reversing flow switch.R 408.30544
Concrete and masonry foundation dampproofing.Rule 544. Section R406.1 of the code is amended to read as follows:Exception: Parging of unit masonry walls is not required where a material is approved for directapplication to the masonry.Light, ventilation and heating.Rule 544. Section R303.4.2 of the code is amended to read as follows:
R303.4.2. Exhaust openings. Outside exhaust openings shall be located as not to create a nuisance. Exhaust openings shall not be directed onto walkways. Exhaust openings shall not terminate within 2 feet of a ventilated section in a soffit.
R 408.30545
Exterior covering.Rule 545. Sections R703.2, R703.6, and R703.8, and table R703.4 of the code are amended to read asfollows:R703.2. Weather-resistive sheathing paper. A minimum of one layer of No. 15 asphalt felt complyingwith ASTM D 226, as listed in chapter 43, for type 1 felt or other approved weather-resistive materialsshall be applied over sheathing of all exterior walls. See table R703.4. Such felt or material shall beapplied horizontally, with the upper layer lapped over the lower layer not less than 2 inches (51 mm).Where joints occur, felt shall be lapped not less than 6 inches (152 mm). Building paper or otherapproved material shall be continuous up to the underside of the rafter or truss top chord and terminatedat penetrations and building appendages in such a manner to meet the requirements of the exterior wallenvelope as described in section R703.1.Exception: Such felt or material is permitted to be omitted in detached accessory buildings.Table R703.4WEATHER-RESISTANT SIDING ATTACHMENT AND MINIMUM THICKNESSSIDINGMATERIALNOMINALTHICKNESSa(INCHES)JOINTTREATMENTSHEATHINGPAPERREQUIREDTYPE OF SUPPORTS FOR THE SIDINGMATERIAL AND FASTENERSbcdWoodorWoodStructuralPanelsheathingFiberboardSheathingIntostudGypsumSheathing IntostudFoamPlasticSheathingIntostudDirecttostudsNumber orSpacing offastenersHorizWitho0.019fLapYes0.1200.1200.1200.120NotSameutnailnail2” longnailzalloweasInsula1½”2” longdstudontaltionlongspaciAlumi0.024LapYes0.120nail1½”long0.120nail2” long0.120nail2” long0.120nailzNotallowedngnumcWith0.019LapYes0.1200.1200.1200.1200.120Insulanailnailnailnailznailtion1½”2½”2½”1½”longlonglonglongHardboardlPanel siding-vertical7/16Note gYesNote oNote oNote oNoteoNote o6”paneledges12”inter.Sup.pHardboardlLap-siding-horizontal7/16Note rYesNote qNote qNote qNoteqNoteqSameasstudspacingSteeli29ga.LapYes0.1130.1130.1130.113NotSamenailnailnailnailzalloweas1¾”2¾”2½”2½StdstudStaple-Staple-Staple-aplezspaci1¾”2 ½”2 ¼”ngParticleboardpanels3/8-1/2Note gYes6d boxnail6d boxnail6d boxnailBoxnailz6dboxnail,3/8notallowed6”paneledge12”inter.Sup.5/8Note gYes6d boxnail8d boxnail8d boxnailboxnailz6dboxnailPlywood panelj(exteriorgrade)3/8Note gYes0.099nail-2”0.113nail-2½”0.099nail-2”0.113nailzStaplez0.099nail-2”6” onedgesVinyl Sidingn0.035LapYes0.1200.1200.120.0120NotSamenailnail 2”nail 2”nailzalloweas1½”Staple-Staple-StapldstudStaple-2½”2½”ezspaci1¾”ngWoodkRustic,3/8 MinLapYesFastener penetration into stud-1”0.113Facedropnail-nailinShiplap19/32AverageLapYes2½”Staple-2”g upto 6”widths, 1nailBevel7/16Butt tip3/16LapYesperbearing;8”widths andover,2nailsperbearingBrick veneer2SectionYesSee Section R703 and Figure R703.7h
Concrete2R703(Note m)masonryveneerStone veneer2SectionR703Yes(Note m)See Section R703 and Figure R703.7h
Fiber cementpanel sidings5/16Note tYes6dcorrosionresistantnailu6dcorrosionresistant nailu6dcorrosionresistant nailu4 dcorrosionresistantnailv6” oconedges, 12”oc onintermed.StudsFiber cementlap sidings5/16Note wYesNotey6dcorrosionresistantnailu6dcorrosionresistant nailu6dcorrosionresistant nailu6dcorrosionresistantnailxNotexFor SI: 1" = 25.4 mma. Based on stud spacing of 16 inches on center where studs are spaced 24 inches, siding shall beapplied to sheathing approved for that spacing.b. Nail is a general description and shall be T-head, modified round head, or round head with smoothor deformed shanks.c. Staples shall have a minimum crown width of 7/16-inch outside diameter and be manufactured ofminimum 16 gage wire.d. Nails or staples shall be aluminum, galvanized, or rust-preventative coated and shall be driven intothe studs for fiberboard or gypsum backing.e. Aluminum nails shall be used to attach aluminum siding.f. Aluminum (0.019 inch) shall be unbacked only when the maximum panel width is 10 inches and themaximum flat area is 8 inches. The tolerance for aluminum siding shall be +0.002 inch of the nominaldimension.g. Sheathing paper required.h. All attachments shall be coated with a corrosion-resistive coating.i. Shall be of approved type.j. Three-eights-inch plywood shall not be applied directly to studs spaced greater than 16 inches oncenter when long dimension is parallel to studs. One-half-inch plywood shall not be the face grainperpendicular to the studs or over sheathing approved for that stud spacing.k. Wood board sidings applied vertically shall be nailed to horizontal nailing strips or blocking set 24inches on center. Nails shall penetrate 1.5 inches into studs, studs and wood sheathing combined, orblocking. A weather-resistant membrane shall be installed weatherboard fashion under the verticalsiding unless the siding boards are lapped or battens are used.l. Hardboard siding shall comply with AHA A135.6 as listed in chapter 43.m. For masonry veneer, a weather-resistant sheathing paper is not required over a sheathing thatperforms as a weather-resistive barrier when a 1-inch air space is provided between the veneer and thesheathing. When the 1-inch space is filled with mortar, a weather-resistant sheathing paper is requiredover studs or sheathing.n. Vinyl siding shall comply with ASTM D 3679 as listed in chapter 43.o. Minimum shank diameter of 0.092 inch, minimum head diameter of 0.025 inch, and nail lengthshall accommodate sheathing and penetrate framing 1.5 inches.p. When used to resist shear forces, the spacing must be 4 inches at panel edges and 8 inches oninterior supports.q. Minimum shank diameter of 0.099 inch, minimum head diameter of 0.240 inch, and nail lengthshall accommodate sheathing and penetrate framing 1.5 inches.r. Vertical end joints shall occur at studs and shall be covered with a joint cover or shall be caulked.s. Fiber cement siding shall comply with the requirements of ASTM C 1186 as listed in chapter 43.t. See section R703.10.1 of the code.u. Minimum 0.102 inch smooth shank, 0.255 inch round head.v. Minimum 0.099 inch smooth shank, 0.250 inch round head.w. See section R703.10.2 of the code.x. Face nailing: 2 nails at each stud. Concealed nailing: one 11 gage 1-1/2 galvanized roofing nail(0.371 inch head diameter, 0.120 inch shank) or 6d galvanized box nail at each stud.y. See exceptions in section R703.2 of the code.z. Minimum nail length shall accommodate sheathing and penetrate framing 1.5 inches.R703.6. Exterior plaster. Installation of these materials shall be in compliance with ASTM C 926,which is adopted by reference in these rules and ASTM C 1063, as listed in chapter 43. The ASTM C926 standard is available for inspection at the Michigan Department of Labor & Economic Growth,Bureau of Construction Codes and Fire Safety, 2501 Woodlake Circle, Okemos, Michigan 48864, orfrom ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA, 19428, at a cost as of thetime of adoption of these amendatory rules of $30.00.R703.6.3. Weather-resistant barriers. Weather-resistant barriers shall be installed as required insection R703.2 and, where applied over wood-based sheathing, shall include a weather-resistive vaporpermeable barrier with a performance at least equivalent to 2 layers of grade D paper.R703.8. Flashing. Approved corrosion-resistive flashing shall be provided in the exterior wallenvelope in such a manner as to prevent entry of water into the wall cavity or penetration of water to thebuilding structural framing components. The flashing shall extend to the surface of the exterior wallfinish and shall be installed to prevent water from reentering the exterior wall envelope. Flashing shallextend to, or beyond, the finished exterior face of the wall. Approved corrosion-resistive flashing shallbe installed at all of the following locations:1. At top of all exterior window and door openings in such a manner as to be leakproof, except thatself-flashing windows having a continuous lap of not less than 1 1/8 inches (28 mm) over the sheathingmaterial around the perimeter of the opening, including corners, do not require additional flashing; jambflashing may also be omitted when specifically approved by the building official.2. At the intersection of chimneys or other masonry construction with frame or stucco walls, withprojecting lips on both sides under stucco copings.3. Under and at the ends of masonry, wood, or metal copings and sills.4. Continuously above all projecting wood trim.5. Where exterior porches, decks, or stairs attach to a wall or floor assembly of wood-frameconstruction.6. At wall and roof intersections.7. At built-in gutters.Exterior covering.Rule 545. Sections R703.7.3, R703.7.4.1, 703.7.5 and R703.7.6 and figures R703.7, R703.7.2.1,
and R703.7.2.2, of the code are amended to read as follows:
R703.7.3. Lintels. Masonry veneer shall not support any vertical load other than the dead load of the veneer above. Veneer above openings shall be supported on lintels of noncombustible materials and the allowable span shall not exceed the values set forth in Table R703.7.3 of the code. The lintels shall have a length of bearing not less than 4 inches (102 mm). Steel lintels shall be corrosion-resistant.
R703.7.4.1. Size, spacing, and corrosion protection. Veneer ties, if strand wire, shall not be less in thickness than no. 9 U.S. gauge [(0.148 in.) (4 mm)] wire and shall have a hook embedded in the mortar joint, or if sheet metal, shall be not less than no. 22 U.S. gauge [(0.0299 in.) (0.76 mm)] by 7/8 inch (22 mm) corrugated. Each tie shall be spaced not more than 24 inches (610 mm) on center horizontally and vertically and shall support not more than 2.67 square feet (0.25 m2) of wall area. Corrosion protection shall be provided for all veneer ties as required by section R606.15.1 of the code.
703.7.5. Flashing. Approved flashing shall be installed beneath the first course of masonry above finished ground level above the foundation wall or slab and at other points of support, including structural floors, shelf angles and lintels when masonry veneers are designed in accordance with section R703.7 of the code. See section R703.8 of the code for additional requirements.
R703.7.6. Weepholes. Weepholes shall be provided in the outside wythe of masonry walls at a maximum spacing of 33 inches (838 mm) on center. Weepholes shall not be less than 3/16 inch (5 mm) in diameter. Weepholes shall be located immediately above and directly on the flashing.
R 408.30546 Smoke alarm locations.
Rule 546. Sections
R313.34 andR313.-4-5 of the code areaddedamended to readthe codeas follows:R313.34. Smoke alarm locations in existing buildings constructed before November 6, 1974. Within each dwelling unit or sleeping unit, a single-station smoke alarm shall be installed in the following locations:1. In each sleeping room or each area directly outside the sleeping room.
2. On each floor level including the basement level.
For sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than 1 full story below the upper level.
R313.-4-5. Equipment requirements. The required equipment for smoke alarms shall consist of thefollowing:
1. Installation. Smoke alarm devices shall be listed and installed in accordance with the manufacturer’s installation requirements, the provisions of the code and the provisions of NFPA 72
which is adopted by reference in these rulesas listed in chapter 43.Thestandard is available forinspection at the Michigan Department of Labor & Economic Growth, Bureau of Construction Codesand Fire Safety, 2501 Woodlake Circle, Okemos, Michigan, 48864, or from NFPA, 1 BatterymarchPark, Quincy, MA, 02269-9101, at a cost as of the time of adoption of these amendatory rules of $-48.00.2. Power Source. The equipment shall be operable by power from 1 of the following primary sources.
a. The building wiring provided that such wiring is served from a commercial source and is equipped with a battery backup. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection.
b. A non-rechargeable battery that is capable of operating the smoke alarm in the normal condition for a life of 5 years.
c. A rechargeable battery, with proper charging, able to power the alarm for a life of 5 years and shall be automatically recharged by an AC circuit of the commercial light and power source.
d. A household use alarm system with battery backup listed and approved in accordance with the household fire warning equipment provisions of NFPA 72, as referenced in Section R313.4 of the code.
3. Audible Alarm Notification. The activation of the alarm signal shall produce a sound that is audible in all occupiable dwelling areas.
4. Testing and Maintenance. The owner of a dwelling unit, in which required or optional fire detection or fire protection systems equipment is installed, shall be responsible for the proper operation, testing, and maintenance of the equipment in accordance with the manufacturer’s instructions included with the equipment. The occupant of rental dwelling units shall be responsible for the periodic operational testing and periodic cleaning of the installed equipment within the rental unit in accordance with the testing instructions provided in the manufacturer’s instructions for the equipment. If the system fails, breaks, or is out of service, it shall be repaired and functional within 30 days.
Exception: Smoke alarms and devices installed in buildings constructed before November 6, 1974 where an installation was approved by the appropriate enforcing agency under regulations in effect at the time of the installation shall be considered to comply with the provisions of the code.
R 408.30547.
Referenced standardsBarrier requirements.Rule 547.
The TPI standard in chapter 43 of the code is amended to update the standard to the TPI 1-2002 editionSection AG105.5 of the code is amended to read as follows.Section AG105.5. Barrier exceptions. Spas or hot tubs with a safety cover which complies with ASTM F 1346, as listed in section AG107 of the code, shall be exempt from the provisions of sections AG105.2, AG105.3, and AG105.4 of the code.
Document Information
- Rules:
- R08.30499
R08.30901
R08.30998
R301.2
R303.4
R311.4
R311.6
R313.4
R323.1
R323.2
R403.1
R403.3
R408.30401
R408.30518
R408.30520
R408.30521
R408.30522
R408.30525
R408.30526
R408.30528
R408.30529
R408.30530
R408.30531
R408.30534
R408.30536
R408.30539
R408.30540
R408.30543
R408.30544
R408.30545
R408.30546
R408.30547
R408.30701
R408.30796
R408.30801
R408.30880
R408.4001
R408.5507
R408.6
R408.7001
R408.8695
R602.10
R606.15
R703.7
R703.8
R905.2
R905.4
R905.5
R905.6
R905.7
R905.8