Section 408.30544b. Exterior walls.  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • b. Section R302.5.1 of the code is amended and table R302.1(1) is added to read as follows:

    R302.5.1. Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 1 3/8 inches (35 mm) in thickness, solid or honeycomb-core steel doors not less than 1 3/8 inches (35 mm) thick, or 20-minute fire-rated doors.

    TABLE R302.1(1) EXTERIOR WALLS

    EXTERIOR WALL ELEMENT

    MINIMUM FIRE- RESISTANCE RATING

    MINIMUM FIRE SEPARATION

     

     

    DISTANCE

    Walls

    Fire-resistance rated

    1 hour-tested in accordance with ASTM E 119 or UL 263 with exposure from both sides

      

    < 5 feet

    Not fire-resistance rated

    0 hours

    5 feet

      

    Projections

    Not alloweda

    NA

    < 2 feet

    Fire-resistance rated

    1 hour on the underside

    2 feet to < 5 feet

    Not fire-resistance rated

    0 hours

    5 feet

    Opening in walls

    Not allowed

    N/A

    < 3 feet

    25% maximum of wall

    area

    0 hours

    3 feet

    Unlimited

    0 hours

    5 feet

    Penetrations

    All

    Comply with Section R302.4

    < 5 feet

    None required

    5 feet

    For SI: 1 foot = 304.8 mm N/A = Not applicable

    a.   except as allowed as per Section R302.1 exceptions 3 and 4

History: 2004 AACS; 2010 AACS; 2015 AACS.